07201353 Permit File
Office CITY OF DUBLIN
RECEI ViEQof Building Standards • 5800 Shier-Rings Road • Dublin, Ohio 43016
Phone: (614) 410-4670 • Inspection Line: (614) 410-4680
SE:P 19 2007 WTFD: (614) 652-3920
BUILDING DIVISION r
CITY OF DUBLIN FIRE PROTECTION PERMIT APPLICATION
Application Date W9w / Bldg. App. #0-IkO 3 Fire Protection App. # Q 4• iDI LW3
PROJECT INFORMATION i
Project Address s5 lxle t~ / ~9c r t_,/L4, k- Project Name? lQST( -y,0_v S
Owner/Tenant Contact Name Telephone
APPLICANT INFORMATIONJJ /
Fire Protection Contractor
Address &"Ccke 9 elf. Telephone `f - ~'7
State Certificate Nu ber y V-5 13 1/2 Dublin Registration Number
Installer Name Non/ ~YJu AV State Certificate Number; ~5
SCOPE OF WORK
(Mark One) New ~ Replace Repair Alteration
FIRE DETECTION AND ALARM SYSTEM (Number of Each)
Detectors Strobes Horns Fire Alarm Boxes Other , h-C6 e
SUPPRESSION SYSTEM (Number of Each)
Standpipes On Site Water Piping Sprinkler Heads Limited Area Other
FEES
FIRE DETECTION OR SUPPRESSION PERMIT PROCESSING FEE $60.00
LOW VOLTAGE PERMIT (DETECTION ONLY) $30.00 Minimum fee
plus $20.00 each 1,000 sq ft or fraction thereof over 1,000 sq ft
OUTSIDE PLAN REVIEW SERVICES (EXAMINER'S FEE AS CHARGED) 150.00
STATE SURCHARGE (3%) W •'-750
TOTAL FEE DUE a\lQ .--Sfl
This permit is granted on the express condition that said work shall in all respects, conform to the ordinances of
the City of Dublin and all laws of the State of Ohio regulating construction, installation, repair and alteration,
and may be revoked at any time upon violation of any provisions of said laws. This permit conveys no right to
open any street, alley or sidewalk or any part thereof, nor to make any connection to a water main.
Signature of Licensed Contractor yZ Z----__ DATE
Print Name f'U: ~t~.~r? DATE
FOR OFFICIAL USE ONLY
Review Comments: The 611,- r s ' / ' s / o r4wi s
Nk- w me e Qr P x ~rP
Fire Department: f/;r Ors Date: ~o s O
Plans Examiner: Date: C> }
Issued by CBO: Date:
Z
. R - CITY OF DUBLIN
Division of Building Standards • 5800 Shier-Rings Road • Dublin, Ohio 43016
Phone: (614) 410-4670 • Inspection Line: (614) 410-4680
Application Number . . . . . 07-00201403 Date 10/02/07
Property Address . . . . . . 655 METRO PL S
Parcel Number: 273-002483
Alternate Address: METRO CENTER
Tenant nbr, name . . . . . . PLASTEKARDS DETECTION
Application type description FIRE PROTECTION
Property owner . . . . . . . CB RICHARD ELLIS
Contractor . . . . . . . . . KEVIN MORGAN ELECTRIC
Permit . . . . . . FIRE DETECTION PERMIT
Additional desc . .
Permit Fee . . . . 60.00 Plan Check Fee .00
Issue Date . . . . Valuation . . . . 0
Qty Unit Charge Per Extension
BASE FEE 60.00
Special Notes and Comments
CONTACT WASHINGTON TOWNSHIP FIRE
PREVENTION FOR INSPECTIONS AT 766-0857
Other Fees . . . . . . . . . OUTSIDE PLAN REVIEW 150.00
SURCHARGE FEE - BLDG 4.50
SURCHARGE FEE - FIRE 1.80
Fee summary Charged Paid Credited Due
Permit Fee Total 60.00 .00 .00 60.00
Plan Check Total .00 .00 .00 .00
Other Fee Total 156.30 .00 .00 156.30
Grand Total 216.30 .00 .00 216.30
4;~ 1
This permit is granted on the express condition that said work shall in all respects,
conform to the ordinances of the City of Dublin and all laws of the State of Ohio
regulating construction, installation, repair and alteration and may be revoked at
any time upon violation of any provisions of law.
CITY OF DUBLIN
Building Standards - 5800 Shier-Rings Road - Dublin, Ohio 43016
Phone: (614) 410-4670 - Inspection Line: (614) 410-4680
Application #07-201403 September 28, 2007
PLAN APPROVAL
FIRE ALARM/DETECTION SYSTEM
THIS IS NOT A BUILDING PERMIT. IT IS A RECORD OF OUR REVIEW OF DOCUMENTS
SUBMITTED WITH YOUR APPLICATION FOR A BUILDING PERMIT.
Re: Plasticard - Fire Alarm System Applicant: Kevin Morgan Electric LLC
655 Metro Place South, Suite 390 (614) 374-9676
Fire Protection Permit No: 07-201403
The Fire Alarm Drawings, submitted with the Fire Protection Permit Application, for the captioned project, has
been reviewed for compliance with the provisions of the 2007 Ohio Building Code (OBC). The review was based
upon the following criteria:
Use Group: B, Business office.
Occupancy: No Change
Area: No Change
Const. Type: II B, Noncombustible-Unprotected
Notes: New Fire Alarm/Detection System for the new Tenant Space in this existing building.
The fire protective signaling system drawings have been Certified by Robert G. Sines III, Ohio certification no.
F-032, the fire protection Contractor is Kevin Morgan Electric LLC, Ohio certification #54-45-1349, the installer
has been identified as Kevin Morgan, Certification #24580, all to comply with the requirements of OBC Section
105.3 and have been reviewed, therefore, in accord with OBC section 105.3.1.4.
This PLAN APPROVAL for the fire protective signaling system only, is issued by the City of Dublin, Division
of Building Standards, in accordance with Section 106.3.1 OBC.
For the information of the Applicant the following item(s) are required for code compliance, but are not
necessarily covered in detail in the construction documents This list is a reminder to the design professional
and contractors of issues which are to be satisfactorily dealt with in the field:
1. The certificate of approval of fire protection plans shall be posted in a conspicuous location outside of the
building or in the front part of the premises on which is, or will be, located the approved building or
equipment. The owner and the contractor shall, so far as possible, preserve and keep said certificate until
the completion of the work to which the approved construction documents relate; Section 105.7.2 OBC.
2. The proposed construction shall conform to the requirements of Chapter I I OBC and the "Americans with
Disabilities Act Accessibility Guidelines" (ADAAG).
City of Dublin FIRE PROTECTION PLAN REVIEW 07-201403
Plasticard - Fire Alarm System September 28, 2007
07-201403 Page 2
3. Fire Alarm System cable and wiring located in noncombustible plenums shall meet with the requirements
of Section 907 OBC and Article 760, NFPA 70.
4. Provide a record of completion for each completed fire alarm system in accordance with Section 907.17
and NFPA 72 Completion Documents.
5. Upon completion of the fire protective signaling system, all alarm-initiating devices and circuits, alarm-
indicating appliances and circuits, supervisory-signal initiating devices and circuits, signaling line circuits,
and primary and secondary power supplies shall be subjected to a 100 percent acceptance test in
accordance with NFPA 72A and 72E listed in Chapter 35; Section 907.16 OBC.
6. OBC 907 Acceptance testing: When the installation of the detectors is complete, each detector and all
interconnecting wiring for multiple-station detectors shall be subject to a 100-percent acceptance test in
accordance with the household fire warning equipment provisions of NFPA 72 listed in Chapter 35.
7. No electrical work (conduits, cables or other electrical apparatus) may be covered or concealed without
visual inspection and approval by the electrical field inspector as per OBC 109.
8. The existing electrical conductors, if removed, abandoned, or altered, shall be accomplished to the
electrical field inspectors approval pursuant to the requirements of Section 109 OBC. Electrical work
found not to meet the code's standards shall be corrected to the electrical field inspector's approval.
9. All electrical work will comply with the requirements of Article 27 OBC and the National Electric Code
NFPA 70, OBC approved edition and is subject to the approval of the electrical inspector, in accordance
with Section 109 of the OBC.
TO REQUEST AN APPEAL HEARING, YOU MUST send a written request, listing the items to be
appealed and the relief sought and on copy of this order to:
Jeffrey S. Tyler, Chief Building Official
City of Dublin, Ohio
5800 Shier Rings Road
Dublin, Ohio 43017-1236
THE SIGNING OF THIS DOCUMENT IS AN AGREEMENT THAT YOU WILL COMPLY WITH ALL
ITEMS LISTED HEREIN. THE COMMENCEMENT OF WORK CONSTITUTES ACCEPTANCE OF ALL
ITEMS LISTED HEREIN.
Reviewed and signed,
411~~d
yler, Chief Building Official
Michael A. Boryca, Architect/Plans E aminer Jeffr
(614) 488-4009 City o blin, Ohio
City of Dublin FIRE PROTECTION PLAN REVIEW 07-201403
Plasticard - Fire Alarm System September 28, 2007
07-203 Page 3
Siwtune - Architect, Engineer, Contractor ate
or ner
Print Name and Title s Signed
c: Washington Township Fire Department
MAB:Iwb
City of Dublin FIRE PROTECTION PLAN REVIEW 07-201403
architecture! memorandum invoice #07-201403 -1
OHIO INCORPORATED 454 East Main Street Suite 236 Columbus, Ohio 43215-5380 614.488.4009 fax.488.4005
September 28, 2007 City of Dublin Contract No. PS 01-21-13
Employer Identification No. 31-1413248
City of Dublin
Division of Building Standards
5800 Shier-Rings Road
Dublin, Ohio 43016
Attention: Mr. Jeffrey S. Tyler, Chief Building Official
Plan Review Services for: Plasticard - Fire Alarm System Alterations
655 Metro Place South, Suite 390
PLAN APPROVAL
Permit No. 07-201403
Labor Cost: Total Number of Hours to be Charged @ $60.00/Hour: 2.5
• Review Time: 1.5
• Administration Time: 1.0
TOTAL BILLING THIS INVOICE $150.00
This memorandum invoice is being sent as reference for you to prepare the necessary fees for the applicant to
pay. The time spent on this review will be submitted for payment at the end of the month with our usual
invoicing. Should you have any questions or comments concerning this review, please don't hesitate to
contact me.
Thank you for the opportunity to be of service.
Cordially,
architecture!
Michael A. Boryca, Architect
Plans Examiner 0001794
CITY OF DUBLIN
RECE~ViEQof Building Standards • 5800 Shier-Rings Ro ' ,Ohio-430-16-
Phone: (614) 410-4670 • Inspection Line: ( Q~
SEP 19, 2001 WTFD: (614) 652-3920''- " '
BUILDING DIVISION SEP 2 4 2007
CITY OF DUBLIN FIRE PROTECTION PERMIT APPLIC TIO t cl- f) C- c tic re!
Application Date 9w Bldg. App. #o •a0 3S3 Fire Protection App. #
PROJECT INFORMATION i ~1~
b ?k9c Project Name? taJ~e-y"Q s
Project Address ,5s Ne)
Owner/Tenant Contact Name Telephone
APPLICANT INFORMATION
Fire Protection Contractor
Address ' i? d/ . d 6d Telephone -
State Certificate Nu ber S'/ Vs 13<19 Dublin Registration Number
Installer Name State Certificate Number c,7 i4-54V
SCOPE OF WORK
(Mark One) New = Replace Repair Alteration
FIRE DETECTION AND ALARM SYSTEM (Number of Each)
Detectors Strobes Horns Fire Alarm Boxes Other di;~? _ e.
SUPPRESSION SYSTEM (Number of Each)
Standpipes On Site Water Piping Sprinkler Heads Limited Area Other
FEES
FIRE DETECTION OR SUPPRESSION PERMIT PROCESSING FEE $60.00
LOW VOLTAGE PERMIT (DETECTION ONLY) $30.00 Minimum fee
plus $20.00 each 1,000 sq ft or fraction thereof over 1,000 sq ft
OUTSIDE PLAN REVIEW SERVICES (EXAMINER'S FEE AS CHARGED)
STATE SURCHARGE (3%)
TOTAL FEE DUE
This permit is granted on the express condition that said work shall in all respects, conform to the ordinances of
the City of Dublin and all laws of the State of Ohio regulating construction, installation, repair and alteration,
and may be revoked at any time upon violation of any provisions of said laws. This permit conveys no right to
open any street, alley or sidewalk or any part thereof, or to make any connection to a water main.
Signature of Licensed Contractor /C4---- DATE
Print Name Zet) DATE 9/e
FOR OFFICIAL USE ONLY
Review Comments:
Fire Department: Date:
Plans Examiner: Date: q• ze •0q
Issued by CBO: Date: