07200565 Permit File
CITY OF DUBLIN
Division of Building Standards • 5800 Shier-Rings Road • Dub!' ie-43
Phone: (614) 410-4670 • Inspection Line: (614) -4680
r WTFD: (614) 889-2347 RSV iSO~ f~l~/i`u>N~S
Applicant &.bb,% ted ( /0 3 ;0'0-
FIRE PROTECTION PERMIT APPLICATI
Application Date 4 /a2 /p7 Bldg. Apo, # Fire Protection App. # • 100 Yp'S_
FROJECT INFORMATION
Proje:.,tAddress (n 1D ~~r.iP~ 'j=jt L+J~ Project Name Me-Air-•'-!
Owner/Tenant Contact Name &d ao(,lt Cr3 s Ry 'i G~ ls~v i Telephone 41cf -4-51-17 70
t
APPLICANT INFORMATION
Fire Protection Contractor Pe JOn) ad-f i c 60
Address A $ ~ 3oIiNSfawnr rid - ~o is, ~ 6 h 42>..2 1-7 Telephone 1614 -4 7S-y4Ill
State Certificate Number 3- S ° 1 IQ ( Dublin Registration Number 41o - 84
Installer Name Pabeat lrck5fesA)- State Certificate Number _5µ-d5-1$11;
SCOPE OF WORK
(Mark One) New X Replace : Repair Alteration
FIRE DETECTION AND ALARM SYSTEM (Number of'Each)-
Detectors Strobes ((a Horns aka, Fire Alarm Boxes Other
SUPPRESSION SYSTEM (Number of Each)
Standpipes On Site Water Piping Sprinkler Heads Limited Area Other
FEES
FIRE DETECTION OR SUPPRESSION PERMIT PROCESSING FEE
LOW VOLTAGE PERMIT (DETECTION ONLY) $30.00 Minimum fee;
plus $20.00 each 1,000 sq ft or fraction thereof over 1,000 sq ft
OUTSIDE PLAN REVIEW SERVICES (EXAMINER'S FEE AS CHARGE.) A,%5. CG
STATE SURCHARGE (3%) 33/000 = . it TOTAL FEE DUE This permit is granted on the express condition that said work shall in all respects, conform to the ordinances of
the City of Dublin and all laws of the State of Ohio regulating construction, installation, repair and allg ration,
and rray be revoked at any time upon violation of any provisions of said laws. This permit con 4,. riht#
open any, street, alley or sidewalk or any part thereof, nor to make anj~ connec#ictn to a water aip(.
Signatur,~~@i@N&;ontractor~-%~ D
I
FOR OFFICIAL USE ONLY , ,~N 17 200$
ELI'.: )1N D VISION
Review Comments: c t t = t? ter r , /c i-~ i~
TI' ~1 t I' x.?t F+ f1(!i /.F` /l?GGl i r,! 7 < / , ; rt
?y r 6,1 IAC- sf yt F _Lt/ 75 visC-cl: drown re e ' r / /7 08 aj.elel PVaM"1'7 /1 oWa h,i Fiie La
ovo? . x
Fire Department:!. Date: L'7P X30
Plans Examiner: t Date:'."J 7
Issued byCBO: Date: 'a&jfi
I
CITY OF DUBLIN
Division of Building Standards - 5800 Shier-Rings Road - Dublin, Ohio 43016
Phone: (614) 410-4670 - Inspection Line: (614) 410-4680
Application Number . . . . . 07-00200565 Date 5/03/07
Property Address . . . . . . 6810 PERIMETER DR
Parcel Number: 273-011310
Alternate Address: PERIMETER WEST PROF PARK
Tenant nbr, name . . . . . . PERIMETER W MED CTR DECTE
Application type description FIRE PROTECTION
Property owner . . . . . . . PERIMETER WEST PROPERTIES LLC
Contractor . . . . . . . . . BEDROCK GROUP DEVELOPMENT
Permit . . . . . . LOW VOLTAGE ELECTRIC PERMIT
Additional desc .
Permit Fee . . 670,00 Plan Check Fee .00
Issue Date . . . . c,~p 'Valuation . . . . 0
Expiration Date 10.0/07,."
Qty Unit Charge Per Extension
BAS E `S'EE 30.00
32.00 20 06'00``THOU COM ELECTRIC LOW VOLTAGE 640.00
Permit FIRE DETECTION PERMIT
Additional desc .
Permit Fee . . . . 60.00 Plan Check Fee .00
Issue Date . . . . Valuation . . . . 0
Qty Unit Charge Per Extension
BASE FEE 6 0 . 0 0
Special Notes and Comments .
CONTACT WASHINGTON TOWNSHIP FIRE
PREVENTION FOR INSPECTIONS AT 766-0857
Other Fees . . . . . . . . . OUTSIDE PLAN REVIEW 240.00
SURCHARGE FEE - ELECTRIC 20.10
SURCHARGE FEE - BLDG 7.20
SURCHARGE FEE - FIRE 1.80
Fee summary Charged Paid Credited Due
Permit Fee Total 730.00 .00 .00 730.00
Plan Check Total .00 .00 .00 .00
Other Fee Total 269.10 .00 .00 269.10
Grand Total 999.10 .00 .00 999.10
This permit is granted on the express condition that said work shall in all r ects,
conform to the ordinances of the City of Dublin and all laws of the State of Ohio
regulating construction, installation, repair and alteration and may be revoked at
any time upon violation of any provisions of law.
„.,a~ WASHINGTON TOWNSHIP
FIRE DEPARTMENT
6200 Eiterman Road, P.O. Box 3248
Dublin, Ohio 43016
614-652-3920 • Fax 614-766-2507
Date: /~il/m6Pr-,7
To: Jeff Tyler, Director
City of Dublin
Division of Building Standards
5800 Shier Rings Road
Dublin, Ohio 43016
Re: Washington Township's Fire Department Plan Review
Permit 07-&Q565
Proj ect: Uinefn^ WC .52A NaVI C&/ Cc.,Ar- fF.Zr
Location: 68/o Per,;,,c Ate.
Received: 3~ ocrb6Pr X007
Review Comments:
c P 4-/ coo WM4 /ji
T w i'
end. ' curie ' m
L- v~ 5wtt) ,24uut A-&he:d
Shvu~;
5hdWA;q no6,'N MAMr5
Reviewed By: Z?AW G , File /Y14
Trustees Gene Bostic • Denise Franz King • Charles Kranstuber Fiscal Officer Joyce E. Robinson Chief Allan woo
CITY OF DUBLIN
Building Standards - 5800 Shier-Rings Road - Dublin, Ohio 43016
Phone: (614) 410-4670 - Inspection Line: (614) 410-4680
Application #07-200565(1) November 9, 2007
CORRECTION REQUEST #1
FIRE ALARM/DETECTION SYSTEM
THIS IS NOT A BUILDING PERMIT. IT IS A RECORD OF OUR REVIEW OF DOCUMENTS
SUBMITTED WITH YOUR APPLICATION FOR A BUILDING PERMIT.
Re: Perimeter West Medical Center Applicant: Penn Electric Co.,
First Floor & Rest Shell - (614) 451-1770
6810 Perimeter Drive Fire Protection Permit No: 07-200565(1)
The Revised Fire Alarm Drawings Received on 10/31/07, submitted with the Fire Protection Permit Application,
for the captioned project, has been reviewed for compliance with the provisions of the 2005 Ohio Building Code
(OBC). The review was based upon the following criteria:
Use Group: No Change
Occupancy: No Change
Area: No Change
Const. Type: Existing [No Change]
Notes: Proposed alteration and addition of Fire Alarm System devices for the new layout of the
Tenant space.
The fire protective signaling system drawings have been Certified by Robert G. Sines a Ohio certification no.
F-032, the fire protection Contractor is Penn Electric Company, Ohio certification #53-25-1191, the installer has
been identified as Robert Eckstein, Certification #54-25-1815, all to comply with the requirements of OBC
Section 105.3 and have been reviewed, therefore, in accord with OBC section 105.3.1.4.
Due to violations of the Ohio Building Code (OBC), which may constitute a serious hazard, the City of Dublin,
Division of Building Standards is unable to issue plan approval at this time without the additional information or
corrections indicated below. This CORRECTION REQUEST LETTER is not a disapproval of the plans, but is
a request for clarification and/or modification of the following items:
The following item(s) shall be brought into full conformance with the OBC prior to the issuance of any
conditional or final plan approval.
1. OBC 907.9 Alarm notification appliances: Alarm notification appliances shall be provided and shall be
listed for their purpose. Audible and visual alarms shall be installed in accordance with the "ADAAG"
and NFPA 72.
ADAAG 4.28.1. Alarm systems required to be accessible shall comply with Section 4.28 ADAAG. At a
minimum, visual signal appliances shall be provided in restrooms and any other general usage areas (e.g.,
meeting rooms, auditoriums, corridors, lobbies and any other area for common use.
City of Dublin FIRE PROTECTION PLAN REVIEW 07-200565(1)
Perimeter West Medical Center - Fire Alarm System November 9, 2007
07-200565(1) P Page 2
Provide visual notification appliances in the following "common use" areas:
1. All Exam Room areas including Consult/Exam rooms,
2. All Treatment Rooms,
3. Traction Rooms,
4. Spa and Treatment areas, and
S. Insomnia Clinic areas.
By definition, these areas constitute common use and shall be protected in accordance with the
referenced code sections. Please explain why these rooms would not be provided with visual signal
appliances? Furthermore, audible alarms shall be tested in the field for compliance with Section 907 9.2
OBC pursuant to their vicinity to these areas of common use.
This review does not preclude the necessity to conform with provisions which may have been omitted or
overlooked in the review process, but which are requirements of the code. Ultimate responsibility for legal
compliance with the Standards of Safety rest with the registered design professional, the tenant and the owner.
Plan Approval will be valid only upon receipt by the City of Dublin, Division of Building Standards, of one
signed copy of this addendum.
TO REQUEST AN APPEAL HEARING, YOU MUST send a written request, listing the items to be
appealed and the relief sought and on copy of this order to:
Jeffrey S. Tyler, Chief Building Official
City of Dublin, Ohio
5800 Shier Rings Road
Dublin, Ohio 43017-1236
Reviewed and signed,
Michael A. Boryca, ArchitectlPl Examiner ffr S. er, Chief Building Official
(614) 488-4009 City of Ohio
Signature - Architect; Engineer, Contractor Date
or Owner
Print Name and Title as Signed
c: Washington Township Fire Department
MAB:Iwb
City of Dublin FIRE PROTECTION PLAN REVIEW 07-200565(1)
CITY OF DUBLIN
Building Standards - 5800 Shier-Rings Road - Dublin, Ohio 43016
Phone: (614) 410-4670 - Inspection Line: (614) 410-4680
Application #07-200565 April 27, 2007
CONDITIONAL PLAN APPROVAL
FIRE ALARM/DETECTION SYSTEM
THIS IS NOT A BUILDING PERMIT. IT IS A RECORD OF OUR REVIEW OF DOCUMENTS
SUBMITTED WITH YOUR APPLICATION FOR A BUILDING PERMIT.
Re: Perimeter West Medical Center Applicant: Penn Electric Co.,
First Floor & Rest Shell (614) 451-1770
6810 Perimeter Drive Fire Protection Permit No: 07-200565
The Fire Alarm Drawings dated 3/13/07, submitted with the Fire Protection Permit Application, for the
captioned project, has been reviewed for compliance with the provisions of the 2005 Ohio Building Code (OBC).
The review was based upon the following criteria:
Use Group: No Change
Occupancy: No Change
Area: No Change
Coust. Type: Existing [No Change]
Notes: Proposed alteration and addition of Fire Alarm System devices for the new layout of the
Tenant space.
The fire protective signaling system drawings have been Certified by Robert G. Sines III, Ohio certification no.
F-032, the fire protection Contractor is Penn Electric Company, Ohio certification #53-25-1191, the installer has
been identified as Robert Eckstein, Certification #54-25-1815, all to comply with the requirements of OBC
Section 105.3 and have been reviewed, therefore, in accord with OBC section 105.3.1.4.
This CONDITIONAL PLAN APPROVAL for the fire protective signaling system only, is issued by the City of
Dublin, Division of Building Standards, in accordance with Section 106.3.1.2 OBC.
The following items shall be corrected or addressed on or before May 30, 2007 as a condition on this Plan
Approval.
1. OBC 907.1.1 Construction documents. Construction documents for fire alarm systems shall be
submitted for review and approval prior to system installation. Construction documents shall include, but
not be limited to, all of the following:
1. A floor plan which indicates the use of all rooms.
2. Locations of alarm-initiating and notification appliances.
3. Alarm control and trouble signaling equipment.
4. Annunciation.
5. Power connection.
6. Battery calculations.
City of Dublin FIRE PROTECTION PLAN REVIEW 07-200565
Perimeter West Medical Center - Fire Alarm System April 27, 2007
07-200565
Page 2
7. Conductor type and sizes.
8. Voltage drop calculations.,
9. Manufacturers, model numbers and listing information for equipment, devices and materials.
10. Details of ceiling height and construction. ~gk1~a,j45
11. The interface of fire safety control functions / R D ,0 ~.3r ~D
Please submit information on the Use or Descriptions of the Rooms shown ;ndef the fa st floor, for further
review. This information was missing or was incomplete on the submission , or our review. Please
ubmit this information so that we may continue our review of this application..
For the information o the Applicant the following item(s) are required for code compliance, but are not
necessarily covered in detae7 in the construction documents. This fist is a reminder to the design professional
and contractors of issues which are to be satisfactorily dealt wide in the field:
.2. The certificate of approval of fire protection plans shall be posted in a conspicuous location outside of the
building or in the front part of the premises on which is, or will be, located the approved building or
equipment. The owner and the contractor shall, so far as possible, preserve and keep said certificate until
the completion of the work to which the approved construction documents relate; Section 105.7.2 OBC.
3. The proposed construction shall conform to the requirements of Chapter 11 OBC and the "Americans with
Disabilities Act Accessibility Guidelines" (ADAAG).
4. Fire Alarm System cable and wiring located in noncombustible plenums shall meet with the requirements
of Section 907 OBC and Article 760, NFPA 70.
5. Provide a record of completion for each completed fire alarm system in accordance with Section 907.17
and NFPA 72 Completion Documents.
6. Upon completion of the fire protective signaling system, all alarm-initiating devices and circuits, alarm-
indicating appliances and circuits, supervisory-signal initiating devices and circuits, signaling line circuits,
and primary and secondary power supplies shall be subjected to a 100 percent acceptance test in
accordance with NFPA 72A and 72E listed in Chapter 35; Section 907.16 OBC.
7. OBC 907 Acceptance testing: When the installation of the detectors is complete, each detector and all
interconnecting wiring for multiple-station detectors shall be subject to a 100-percent acceptance test in
accordance with the household fire warning equipment provisions of NFPA 72 listed in Chapter 35.
8. No electrical work (conduits, cables or other electrical apparatus) may be covered or concealed without
visual inspection and approval by the electrical field inspector as per OBC 109.
9. The existing electrical conductors, if removed, abandoned, or altered, shall be accomplished to the
electrical field inspectors approval pursuant to the requirements of Section 109 OBC. Electrical work
found not to meet the code's standards shall be corrected to the electrical field inspector's approval.
10. All electrical work will comply with the requirements of Article 27 OBC and the National Electric Code
NFPA 70, OBC approved edition and is subject to the approval of the electrical inspector, in accordance
with Section 109 of the OBC.
City of Dublin FIRE PROTECTION PLAN REVIEW 07-200565
Perimeter West Medical Center - Fire Alarm System
07-200565 April 27, 2007
Page 3
TO REQUEST AN APPEAL HEARING, YOU MUST send a written request, listing the items to be
appealed and the relief sought and on copy of this order to:
Jeffrey S. Tyler, Chief Building Official
City of Dublin, Ohio
5800 Shier Icings Road
Dublin, Ohio 43017-1236
THIS RECORD OF OUR REVIEW OF DOCUMENTS IS TO BE SIGNED BY THE OWNER OR
HIS/HER AUTHORIZED AGENT AND RETURNED, ALONG WITH ANY REQUESTED
INFORMATION, TO THIS BUILDING DEPARTMENT BEFORE BEGINNING WORK, BUT NOT
MORE THAN 30 DAYS AFTER ISSUANCE. FAILURE TO COMPLY MAY RESULT IN REVOCATION
OF THE BUILDING PERMIT.
THE SIGNING OF THIS DOCUMENT IS AN AGREEMENT THAT YOU WILL COMPLY WITH ALL
ITEMS LISTED HEREIN. THE COMMENCEMENT OF WORK CONSTITUTES ACCEPTANCE OF ALL
ITEMS LISTED HEREIN.
Reviewed and signed,
lMt4&d a /Co..
Michael A. Boryca, Architect/Plans Examiner a S. leer, Chief Building Official
(614) 488-4009 City o lin, Olio
+ 5 Zf --C 7
Signature - Architect, Engin Contractor Date
or Owner 1
l~o~ert,f 14- ~ l~5'fGiN ~2~S,o?eniT
Print Name and Title as Signed
c: Washington Township Fire Department
MAB:Iwb
City of Dublin FIRE PROTECTION PLAN REVIEW 07-200565
CITY OF DUBLIN
Building Standards • 5800 Shier-Rings Road • Dublin, Ohio 43016
Phone: (614) 410-4670 • Inspection Line: (614) 410-4680
Application Number . . . . . 07-00200565 Date 1/30/08
Revision number . . . . . . . 2
Property Address . . . . . . 6810 PERIMETER DR
Parcel Number: 273-011310
Alternate Address: PERIMETER WEST PROF PARK
Tenant nbr, name . . . . . . PERIMETER W MED CTR DETEC
Application type description FIRE PROTECTION
Property owner . . . . . . . PERIMETER WEST PROPERTIES LLC
Contractor . . . . . . . . . BEDROCK GROUP DEVELOPMENT
Permit . . . . . . FIRE DETECTION PERMIT
Additional desc . .
Permit Fee . . . . 60.00 Plan Check Fee .00
Issue Date . . . . 5/04/07 Valuation . . . . 0
Qty Unit Charge Per Extension
BASE FEE 60.00
Special Notes and Comments
CONTACT WASHINGTON TOWNSHIP FIRE
PREVENTION FOR INSPECTIONS AT 766-0857
Other Fees . . . . . . . . . OUTSIDE PLAN REVIEW 525.00
SURCHARGE FEE - ELECTRIC 20.10
SURCHARGE FEE - BLDG 15.75
SURCHARGE FEE - FIRE 1.80
Fee summary Charged Paid Credited Due
Permit Fee Total 60.00 60.00 .00 .00
Plan Check Total .00 .00 .00 .00
Other Fee Total 562.65 269.10 .00 293.55
Grand Total 622.65 329.10 .00 293.55
This permit is granted on the express condition that said work shall in all respects,
conform to the ordinances of the City of Dublin and all laws of the State of Ohio
regulating construction, installation, repair and alteration and may be revoked at
any time upon violation of any provisions of law.
architecture! memorandum invoice #07-200565 - 3
OHIO INCORPORATED 454 East Main Street Suite 236 Columbus, Ohio 43215-5380 614.488.4009 fax.488.4005
January 29, 2008 City of Dublin Contract No. PS 01-21-13
Employer Identification No. 31-1413248
City of Dublin
Division of Building Standards
5800 Shier-Rings Road
Dublin, Ohio 43016
Attention: Mr. Jeffrey S. Tyler, Chief Building Official
Plan Review Services for: Perimeter West Medical Center - Fire Alarm System Alterations
6810 Perimeter Drive
PLAN APPROVAL
Permit No. 07-200565(2)
Labor Cost: Total Number of Hours to be Charged @ $60.00/Hour: 2.25
• Plan Review Time: 0.5
• Discussions w1 Applicant & Fire Marshal: 0.75
• Administrative Time: 1.0
TOTAL BILLING THIS INVOICE $135.00
This memorandum invoice is being sent as reference for you to prepare the necessary fees for the applicant to
pay. The time spent on this review will be submitted for payment at the end of the month with our usual
invoicing.
Should you have any questions or comments concerning this review, please don't hesitate to contact me.
Thank you for the opportunity to be of service.
Cordially,
arc e ture
Michael A. Boryca, Architect
Plans Examiner #P001794
CITY OF DUBLIN
Building Standards - 5800 Shier-Rings Road - Dublin, Ohio 43016
Phone: (614) 410-4670 - Inspection Line: (614) 410-4680
Application #07-200565(2) January 29, 2008
PLAN APPROVAL
FIRE ALARM/DETECTION SYSTEM
THIS IS NOT A BUILDING PERMIT. IT IS A RECORD OF OUR REVIEW OF DOCUMENTS
SUBMITTED WITH YOUR APPLICATION FOR A BUILDING PERMIT.
Re: Perimeter West Medical Center Applicant: Penn Electric Co.,
First Floor & Rest Shell (614) 451-1770
6810 Perimeter Drive Fire Protection Permit No: 07-200565(2)
The Revised Fire Alarm Drawings Received on 1/17/08, submitted with the Fire Protection Permit Application,
for the captioned project, has been reviewed for compliance with the provisions of the 2005 Ohio Building Code
(OBC). The review was based upon the following criteria:
Use Group: No Change
Occupancy: No Change
Area: No Change
Const. Type: Existing [No Change]
Notes: Proposed alteration and addition of Fire Alarm System devices for the new layout of the
Tenant space.
The fire protective signaling system drawings have been Certified by Robert G. Sines III, Ohio certification no.
F-032, the fire protection Contractor is Penn Electric Company, Ohio certification #53-25-1191, the installer has
been identified as Robert Eckstein, Certification #54-25-1815, all to comply with the requirements of OBC
Section 105.3 and have been reviewed, therefore, in accord with OBC section 105.3.1.4.
This PLAN APPROVAL for the fire protective signaling system only, is issued by the City of Dublin,
Division of Building Standards, in accordance with Section 106.3.1 OBC.
For the information of the Applicant the following item(s) are required jot code compliance, but are not
necessarily covered in detail in the construction documents This list is a reminder to the design professional
and contractors of issues which are to be satisfactorily dealt with in the field:
1. A set of construction documents which have been approved under section 105 of the OBC shall be kept at
the site of the work and shall be available for reference by the building official at all times during working
hours while such work is in progress; Section 109 OBC.
2. If substantive changes to the building are contemplated after first document submission, or during
construction, those changes must be submitted to the building official for review and approval prior to the
changes being executed.
City of Dublin FIRE PROTECTION PLAN REVIEW 07-200565(2)
Perimeter West Medical Center - Fire Alarm System January 29, 2008
07-200565(2) Page 2
3. The certificate of approval of fire protection plans shall be posted in a conspicuous location outside of the
building or in the front part of the premises on which is, or will be, located the approved building or
equipment. The owner and the contractor shall, so far as possible, preserve and keep said certificate until
the completion of the work to which the approved construction documents relate; Section 105.7.2 OBC.
4. OBC 901.5 Acceptance tests: All fire protection systems shall be tested in accordance with the
requirements of this code and the International Fire Code. When required, the tests shall be conducted in
the presence of the code official. All tests required by this code and the standards listed in this code shall
be conducted at the expense of the owner or the owner's representative. It shall be unlawful to occupy
portions of a structure until the required fire protection systems within that portion of the structure have
been tested and approved.
5. The proposed construction shall conform to the requirements of Chapter 11 OBC and the "Americans with
Disabilities Act Accessibility Guidelines" (ADAAG).
6. Fire Alarm System cable and wiring shall meet with the requirements of Section 907.5, Chapter 27 OBC
and Article 760, NFPA 70.
7. Provide a record of completion for each completed fire alarm system in accordance with Section 907.17
and NFPA 72 Completion Documents.
8. OBC 907.16 Acceptance Testing. Upon completion of the fire protective signaling system, all alarm-
initiating devices and circuits, alarm-indicating appliances and circuits, supervisory-signal initiating
devices and circuits, signaling line circuits, and primary and secondary power supplies shall be tested in
accordance with NFPA 72.
9. No electrical work (conduits, cables or other electrical apparatus) may be covered or concealed without
visual inspection and approval by the electrical field inspector as per OBC 109.
10. The existing electrical conductors, if removed, abandoned, or altered, shall be accomplished to the
electrical field inspectors approval. Electrical work found not to meet the code's standards shall be
corrected to the electrical field inspector's approval, Section 109 OBC.
11. All electrical work will comply with the requirements of Article 27 OBC and the National Electric Code
NFPA 70, approved edition and is subject to the approval of the electrical inspector, in accordance with
Section 109 of the OBC.
TO REQUEST AN APPEAL HEARING, YOU MUST send a written request, listing the items to be
appealed and the relief sought and on copy of this order to:
Jeffrey S. Tyler, Chief Building Official
City of Dublin, Ohio
5800 Shier Rings Road
Dublin, Ohio 43017-1236
City of Dublin FIRE PROTECTION PLAN REVIEW 07-200565(2)
Perimeter West Medical Center - Fire Alarm System January 29, 2008
07-200565(2) Page 3
Reviewed and signed,
Michael A. Boryca, Architect/Plans xaminer Jeffr yler, Chief Building Official
(614) 488-4009 City o Du lin, Ohio
atnre - Architect, Engineer, Contractor Date
r~Owner
-~-1C ~Yl GIG S i ~
Print Name and Title as Signed
c: Washington Township Fire Department
MAB:Iwb
City of Dublin FIRE PROTECTION PLAN REVIEW 07-200565(2)
CITY OF DUBLIN
Division of Building Standards • 5800 Shier-Rings Road • Dublin, Ohio 43016
Phone: (614) 410-4670 • Inspection Line: (614) 410-4680
WTFD: (614) 889-2347 REV ~5OA~ DA#U)-WN s
Applicant -Shmil1 e.4 /0/6 9
' FIRE PROTECTION PERMIT APPLICATION
Application Date 4 w2 /0 7 Bldg. Apo, # Fire Protection App. # 10_ • 00
PROJECT INFORMATION,
Project Address Project Name M Lj1 c ' I f
Owner/Tenant Contact Name dnb(,h- ~~}.~:stiayC ~ c rauv~3 Telephone 4, /y 1/5 / 17 70
r
APPLICANT INFORMATION
Fire Protection Contractor Pe )y n) & C_ ~_a i c (a
Address A ~a~?NS ¢vw,+~ Pd. GPIs „ C 1t 4 ~,.0 Telephone 0 4 -1f I - q~, ` 1/
State Certificate Number 53_ j S _ j IQ 1 Dublin Registration Number 61o-e4
Installer Name Pobeaf Eckk 5 fe-iA) State Certificate Number.5 4-AS-191,!
SCOPE OF WORK
(Mark One) New Replace Repair Alteration
FIRE DETECTION AND ALARM SYSTEM (Number of 'Each),
Detectors I Strobes ((a Horns Fire Alarm Boxes Other 15
SUPPRESSION SYSTEM (Number of Each)
Standpipes On Site Water Piping Sprinkler Heads Limited Area Other
FEES
FIRE DETECTION OR SUPPRESSION PERMIT PROCESSING FEE
LOW VOLTAGE PERMIT (DETECTION ONLY) $30.00 Minimum fee
plus $20.00 each 1,000 sq ft or fraction thereof over 1,000 sq ft
OUTSIDE PLAN REVIEW SERVICES (EXAMINER'S FEE AS CHARGED)
STATE SURCHARGE (3%) :33600 ~ t
TOTAL FEE DUE ' Is S
This permit is granted on the express condition that said work shall in all respects, conform to the ordinances of
the City of Dublin and all laws of the State of Ohio regulating construction, installation, repair and alteration, -
ell,
and may be revoked at any time upon violation of any provisions of said laws. This permit con * ys, no right tc,_
open any street, alley or sidewalk or any part thereof, nor to make any connection to a water aipr.
Signature of Licensed Contractor P4_10,41 14 r Kl~i D¢I E p4 16?
FOR OFFICIAL USE ONLY
Review Comments: r 7 Ji il; r
a
r~
-,a fe-v~ F•~ : /?CJ~z'~ r !t i f.;'_ %~/y"~"~ ~ / ' • /wry ; - ;;~,,,r,~,~/ ~yjE, ~J,~~ X. /,~,,r/'j
eyl a/ zcreltleW / /7 O h~a flin o l~/I1s`7~
file f~ / `
42
ZLql. v X q
Fire epartment:'~ Date:
Plans Examiner: Date: "7 i c}
Issued by CBO: Date: 11 % 1 vb a
CITY OF DUBLIN
Division of Building Standards - 5800 Shier-Rings Road - Dublin, Ohio 43016
Phone: (614) 410-4670 - Inspection Line: (614) 410-4680
Application Number . . . . . 07-00200565 Date 5/03/07
Property Address . . . . . . 6810 PERIMETER DR
Parcel Number: 273-011310
Alternate Address: PERIMETER WEST PROF PARK
Tenant nbr, name PERIMETER W MED CTR DECTE
Application type description FIRE PROTECTION
Property owner . . . . . . . PERIMETER WEST PROPERTIES LLC
Contractor . . . . . . . . . BEDROCK GROUP DEVELOPMENT
Permit . . . . LOW VOLTAGE ELECTRIC PERMIT
Additional desc .
Permit Fee . . . 670.00 Plan Check Fee .00
Issue Date cw~t Valuation 0
Expiration Date 10 3 07
Qty Unit Charge Per Extension
BASE FEE 30.00
32.00 20.0000 THOU COM ELECTRIC LOW VOLTAGE 640.00
Permit . . . . FIRE DETECTION PERMIT
Additional desc .
Permit Fee . . . . 60.00 Plan Check Fee .00
Issue Date . . . . Valuation . . . . 0
Qty Unit Charge Per Extension
BASE FEE 60.00
Special Notes and Comments
CONTACT WASHINGTON TOWNSHIP FIRE
PREVENTION FOR INSPECTIONS AT 766-0857
Other Fees . . . . . . . . . OUTSIDE PLAN REVIEW 240.00
SURCHARGE FEE - ELECTRIC 20.10
SURCHARGE FEE - BLDG 7.20
SURCHARGE FEE - FIRE 1.80
Fee summary Charged Paid Credited Due
Permit Fee Total 730.00 .00 .00 730.00
Plan Check Total .00 .00 .00 .00
Other Fee Total 269.10 .00 .00 269.10
Grand Total 999.10 .00 .00 999.10
This permit is granted on the express condition that said work shall in all r ects,
conform to the ordinances of the City of Dublin and all laws of the State of Ohio
regulating construction, installation, repair and alteration and may be revoked at
any time upon violation of any provisions of law.
I I
OVSTIES 00 WASHINGTON TOWNSHIP
FIRE DEPARTMENT
6200 Eiterman Road, P.O. Box 3248
"ANKV~ J Dublin, Ohio 43016
614-652-3920 • Fax 614-766-2507
Date: /y ya,, M6911.
To: Jeff Tyler, Director
City of Dublin
Division of Building Standards
5800 Shier Rings Road
Dublin, Ohio 43016
Re: Washington Township's Fire Department Plan Review
Permit 47-~DOS6S /Rcy.&
Project: ri:r~cfn^ Lyest /~lcd. c,/
Location: 68/0 ~°eriih~i- D~
Received: ,3~ oc~~ 007
Review Comments:
Tow i ~
of d~)' 9 07 X arfi°)
L- v, s aN Dal+wiAkie, A-Ghed
how Ng Rom N/AMes
Reviewed By: a~ cff &An:b Fi je /19ors/j~/
Trustees Gene Bostic • Denise Franz King • Charles Kranstuber Fiscal Officer Joyce E. Robinson Chief Allan Woo
CITY OF DUBLIN
Building Standards - 5800 Shier-Rings Road - Dublin, Ohio 43016
Phone: (614) 410-4670 - Inspection Line: (614) 410-4680
Application #07-200565(1) November 9, 2007
CORRECTION REQUEST #1
FIRE ALARM/DETECTION SYSTEM
THIS IS NOT A BUILDING PERMIT. IT IS A RECORD OF OUR REVIEW OF DOCUMENTS
SUBMITTED WITH YOUR APPLICATION FOR A BUILDING PERMIT.
Re: Perimeter West Medical Center Applicant: Penn Electric Co.,
First Floor & Rest Shell (614) 451-1770
6810 Perimeter Drive Fire Protection Permit No: 07-200565(1)
The Revised Fire Alarm Drawings Received on 10/31/07, submitted with the Fire Protection Permit Application,
for the captioned project, has been reviewed for compliance with the provisions of the 2005 Ohio Building Code
(OBC). The review was based upon the following criteria:
Use Group: No Change
Occupancy: No Change
Area: No Change
Const. Type: Existing [No Change]
Notes: Proposed alteration and addition of Fire Alarm System devices for the new layout of the
Tenant space.
The fire protective signaling system drawings have been Certified by Robert G. Sines III, Ohio certification no.
F-032, the fire protection Contractor is Penn Electric Company, Ohio certification #53-25-1191, the installer has
been identified as Robert Eckstein, Certification #54-25-1815, all to comply with the requirements of OBC
Section 105.3 and have been reviewed, therefore, in accord with OBC section 105.3.1.4.
Due to violations of the Ohio Building Code (OBC), which may constitute a serious hazard, the City of Dublin,
Division of Building Standards is unable to issue plan approval at this time without the additional information or
corrections indicated below. This CORRECTION REQUEST LETTER is not a disapproval of the plans, but is
a request for clarification and/or modification of the following items:
The following item(s) shall be brought into full conformance with the OBC prior to the issuance of any
conditional or final plan approval.
1. OBC 907.9 Alarm notification appliances: Alarm notification appliances shall be provided and shall be
listed for their purpose. Audible and visual alarms shall be installed in accordance with the "ADAAG"
and NFPA 72.
ADAAG 4.28.1. Alarm systems required to be accessible shall comply with Section 4.28 ADAAG. At a
minimum, visual signal appliances shall be provided in restrooms and any other general usage areas (e.g.,
meeting rooms, auditoriums, corridors, lobbies and any other area for common use.
City of Dublin FIRE PROTECTION PLAN REVIEW 07-200565(1)
Perimeter West Medical Center - Fire Alarm System November 9, 2007
07-200565(1) Page 2
Provide visual notification appliances in the following "common use areas:
1. All Exam Room areas including Consult/Exam rooms, "S j -6,A f
2. All Treatment Rooms,
3. Traction Rooms, A-u) N9S
4. Spa and Treatment areas, and
S. Insomnia Clinic areas.
By definition, these areas constitute common use and shall be protected in accordance with the
referenced code sections. Please explain why these rooms would not be provided with visual signal
appliances? Furthermore, audible alarms shall be tested in the field for compliance with Section 90 7.9.2
OBC pursuant to their vicinity to these areas of common use.
This review does not preclude the necessity to conform with provisions which may have been omitted or
overlooked in the review process, but which are requirements of the code. Ultimate responsibility for legal
compliance with the Standards of Safety rest with the registered design professional, the tenant and the owner.
Plan Approval will be valid only upon receipt by the City of Dublin, Division of Building Standards, of one
signed copy of this addendum.
TO REQUEST AN APPEAL HEARING, YOU MUST send a written request, listing the items to be
appealed and the relief sought and on copy of this order to:
Jeffrey S. Tyler, Chief Building Official
City of Dublin, Ohio
5800 Shier Rings Road
Dublin, Ohio 43017-1236
Reviewed and signed,
/p4u~ a I J A ~ ~
Michael A. Boryca, Architect/Plan Examiner a er, Chief Building Official
(614) 488-4009 City of b ' Ohio
80644,t - i `17 /08
Signature - Architect, Engineer, Contractor Date
or Owner ' L
Print Name and Title as Signed
c: Washington Township Fire Department
MAB:Iwb
City of Dublin FIRE PROTECTION PLAN REVIEW 07-200565(1)
CITY OF DUBLIN
Building Standards - 5800 Shier-Rings Road - Dublin, Ohio 43016
Phone: (614) 410-4670 - Inspection Line: (614) 410-4680
Application #07-200565 April 27, 2007
CONDITIONAL PLAN APPROVAL
FIRE ALARM/DETECTION SYSTEM
THIS IS NOT A BUILDING PERMIT. IT IS A RECORD OF OUR REVIEW OF DOCUMENTS
SUBMITTED WITH YOUR APPLICATION FOR A BUILDING PERMIT.
Re: Perimeter West Medical Center Applicant: Penn Electric Co.,
First Floor & Rest Shell (614) 451-1770
6810 Perimeter Drive Fire Protection Permit No: 07-200565
The Fire Alarm Drawings dated 3/13/07, submitted with the Fire Protection Permit Application, for the
captioned project, has been reviewed for compliance with the provisions of the 2005 Ohio Building Code (OBC).
The review was based upon the following criteria:
Use Group: No Change
Occupancy: No Change
Area: No Change
Const. Type: Existing [No Change]
Notes: Proposed alteration and addition of Fire Alarm System devices for the new layout of the
Tenant space.
The fire protective signaling system drawings have been Certified by Robert G. Sines III, Ohio certification no.
F-032, the fire protection Contractor is Penn Electric Company, Ohio certification #53-25-1191, the installer has
been identified as Robert Eckstein, Certification #54-25-1815, all to comply with the requirements of OBC
Section 105.3 and have been reviewed, therefore, in accord with OBC section 105.3.1.4.
This CONDITIONAL PLAN APPROVAL for the fire protective signaling system only, is issued by the City of
Dublin, Division of Building Standards, in accordance with Section 106.3.1.2 OBC.
The following items shall be corrected or addressed on or before May 30, 2007 as a condition on this Plan
Approval.
1. OBC 907.1.1 Construction documents. Construction documents for fire alarm systems shall be
submitted for review and approval prior to system installation. Construction documents shall include, but
not be limited to, all of the following:
1. A floor plan which indicates the use of all rooms.
2. Locations of alarm-initiating and notification appliances.
3. Alarm control and trouble signaling equipment.
4. Annunciation.
5. Power connection.
6. Battery calculations.
City of Dublin FIRE PROTECTION PLAN REVIEW 07-200565
Perimeter West Medical Center - Fire Alarm System April 27, 2007
07-200565
Page 2
7. Conductor type and sizes.
8. Voltage drop calculations. 1
9. Manufacturers, model numbers and listing information for equipment, devices and materials.
10. Details of ceiling height and construction. n ~q)~
11. The interface of fire safety control functions D P 013%
I
Please submit information on the Use or Descriptions of the Rooms shown on the first floor, L
r fu
rther
review. This information was missing or was incomplete on the submission made, for our rew. Please
ubmit this information so that we may continue our review of this application..
For the information o the Applicant the following item(s) are required for code compliance, but are not
necessarily covered in detail in the construction documents This list is a reminder to the design professional
and contractors of issues which are to be satisfactorily dealt with in the field:
2. The certificate of approval of fire protection plans shall be posted in a conspicuous location outside of the
building or in the front part of the premises on which is, or will be, located the approved building or
equipment. The owner and the contractor shall, so far as possible, preserve and keep said certificate until
the completion of the work to which the approved construction documents relate; Section 105.7.2 OBC.
3. The proposed construction shall conform to the requirements of Chapter 11 OBC and the "Americans with
Disabilities Act Accessibility Guidelines" (ADAAG).
4. Fire Alarm System cable and wiring located in noncombustible plenums shall meet with the requirements
of Section 907 OBC and Article 760, NFPA 70.
5. Provide a record of completion for each completed fire alarm system in accordance with Section 907.17
and NFPA 72 Completion Documents.
6. Upon completion of the fire protective signaling system, all alarm-initiating devices and circuits, alarm-
indicating appliances and circuits, supervisory-signal initiating devices and circuits, signaling line circuits,
and primary and secondary power supplies shall be subjected to a 100 percent acceptance test in
accordance with NFPA 72A and 72E listed in Chapter 35; Section 907.16 OBC.
7. OBC 907 Acceptance testing: When the installation of the detectors is complete, each detector and all
interconnecting wiring for multiple-station detectors shall be subject to a 100-percent acceptance test in
accordance with the household fire warning equipment provisions of NFPA 72 listed in Chapter 35.
8. No electrical work (conduits, cables or other electrical apparatus) may be covered or concealed without
visual inspection and approval by the electrical field inspector as per OBC 109.
9. The existing electrical conductors, if removed, abandoned, or altered, shall be accomplished to the
electrical field inspectors approval pursuant to the requirements of Section 109 OBC. Electrical work
found not to meet the code's standards shall be corrected to the electrical field inspector's approval.
10. All electrical work will comply with the requirements of Article 27 OBC and the National Electric Code
NFPA 70, OBC approved edition and is subject to the approval of the electrical inspector, in accordance
with Section 109 of the OBC.
City of Dublin FIRE PROTECTION PLAN REVIEW 07-200565
Perimeter West Medical Center - Fire Alarm System April 27, 2007
07-200565
Page 3
TO REQUEST AN APPEAL HEARING, YOU MUST send a written request, listing the items to be
appealed and the relief sought and on copy of this order to:
Jeffrey S. Tyler, Chief Building Official
City of Dublin, Ohio
5800 Shier Rings Road
Dublin, Ohio 43017-1236
THIS RECORD OF OUR REVIEW OF DOCUMENTS IS TO BE SIGNED BY THE OWNER OR
HIS/HER AUTHORIZED AGENT AND RETURNED, ALONG WITH ANY REQUESTED
INFORMATION, TO THIS BUILDING DEPARTMENT BEFORE BEGINNING WORK, BUT NOT
MORE THAN 30 DAYS AFTER ISSUANCE. FAILURE TO COMPLY MAY RESULT IN REVOCATION
OF THE BUILDING PERMIT.
THE SIGNING OF THIS DOCUMENT IS AN AGREEMENT THAT YOU WILL COMPLY WITH ALL
ITEMS LISTED HEREIN. THE COMMENCEMENT OF WORK CONSTITUTES ACCEPTANCE OF ALL
ITEMS LISTED HEREIN.
Reviewed and signed,
IMA4a a '(30u, Michael A. Boryca, Architect/Plans Examiner a S. leer, ief Building Official
(614) 488-4009 City o o
'4- S 7
Signatur e - Architect, Engine Contractor Date
or Owner
_)304e&f A- ~ck51~GrN - ~/1~5~'o~e~vT
Print Name and Title as Signed
c: Washington Township Fire Department
MAB:Iwb
City of Dublin FIRE PROTECTION PLAN REVIEW 07-200565
! 00!cant CITY OF DUBLIN
Division of Building Standards • 5800 Shier-Rings Road 9 Dublin, -Ohio 43016
R E E I VE Q Phone: (614) 410-4670 • Inspection Line: (614) 410-4680
WTFD: (614) 889-2347
APR A 2 2007
BUILDING DIVISION FIRE PROTECTION PERMIT APPLICATION
CITY OF DUB4
Application Date `Z 07 Bldg. App. # Fire Protection App. # 010-:7 • C S~~
PROJECT I F R ATI N PaQ;Me-/~a U9e~t
Project Address 10 a iMefe i u<e Project Name Med ic-+1 Cco0i-
Owner/Tenant Contact Name Bedaotk v f~ofJ ao Telephone 41y - 4151-1770
APPLICANT INFORMAT
Fire Protection Contractor a ~n1 c~ R IC o
Address hN A) 6 .1I Telephone 61q-q76-411,174
State Certificate Number 3-a5 lta I Dublin Registration Number __(U -S
Installer Name J~abeaf e-k5 e-PA) State Certificate Number .54-aS-ISIS
SCOPE OF WORK
(Mark One) New X Replace Repair Alteration
FIRED TECTI N AND ALARM Y (Number of Each)
Detectors Strobes la Horns 41o'L Fire Alarm Boxes _1_ Other
SUPPRESSION SYSTEM (Number of Each)
Standpipes On Site Water Piing Sprinkler Heads Limited Area Other
FEES
too, 00
'RE DETECTION OR SUPPRESSION PERMIT PRQCESSINq
LOW VOLTAGE PERMIT (DETECTION ONLY) $30,0b Minimum fee 30, ao
plus $20.00 each 1,000 sq ft or fraction thereof ov#r 1,000 sq ft
1040 00
OUTSIDE PLAN REVIEW SERVICES (EXAMIIy i'S FEE AS CIAAWO 911 0.017
STATE SURCHARGE (3%) .3 3/000 Atfi O
TOTAL FEE DUE r 1
This permit is granted on the express condition that said work shall in all respects, conform to the ordinances of
the City of Dublin and all laws of the Statq-of Ohio regulating construction, installation, repair and alteration,
and may be revoked at any time upon violation of any provisions of said laws. This permit conveys no right to
open any street, alley or sidewalk or arty part thereof, nor to make any connection to a water main.
Signature of Licensed Contractor /DATE 44116-7
FOR OFFICIAL USE ONLY
Review Comments: e filic a ? /
To
o
se
adme 09
s AV_Am_Z On Ne Ag~~'~r re hifeZ- W*A-al 01T x OIK
e Department: Date: .54107 _
Plans Examiner: I J - Q Date: b
Issued by CBO: Date:
"'O"00%V
• WASHINGTON TOWNSHIP
Cp~NTIES pF •
FIRE DEPARTMENT
6200 Eiterman Road, PO. Box 3248
RF'FRANK~~ Dublin, Ohio 43016
• 1 '
614-652-3920 • Fax 614-766-2507
Date: /y~/oyYmdPr,~i~D7
To: Jeff Tyler, Director
City of Dublin
Division of Building Standards
5800 Shier Rings Road
Dublin, Ohio 43016
Re: Washington Township's Fire Department Plan Review
Permit 07-&CS-6S JIRCVY~ 1o17
Project: AriinmIk ^ We 5,4 /Lmc / c,/ <e~~r-
Location: 6810 PgriihcAr- Ar.
Received: 9/ 00!b6Pr 17007
Review Comments:
7h-e- e vi r ale 17c74 /-Ilee74
i
Towash.,~2 74 0,a9 I-,V 09
~Pend~ixt Co/re cio.~ of iihs n ofQ~ Gy7 /hl i~~Bac.rn s
revs ecy /c~f~/' moron, C• ~`v of A16/.%7 04feW P 07 x~ors~
Reviewed By: Zaw /Y~ArsfjAf
Trustees Gene Bostic • Denise Franz King • Charles Kranstuber Fiscal Officer Joyce E. Robinson Chief Allan Woo
CITY OF DUBLIN
Building Standards - 5800 Shier-Rings Road - Dublin, Ohio 43016
Phone: (614) 410-4670 - Inspection Line: (614) 410-4680
Application #07-200565(1) November 9, 2007
CORRECTION REQUEST #1
FIRE ALARM/DETECTION SYSTEM
THIS IS NOT A BUILDING PERMIT. IT IS A RECORD OF OUR REVIEW OF DOCUMENTS
SUBMITTED WITH YOUR APPLICATION FOR A BUILDING PERMIT.
Re: Perimeter West Medical Center Applicant: Penn Electric Co.,
First Floor & Rest Shell (614) 451-1770
6810 Perimeter Drive Fire Protection Permit No: 07-200565(1)
The Revised Fire Alarm Drawings Received on 10/31/07, submitted with the Fire Protection Permit Application,
for the captioned project, has been reviewed for compliance with the provisions of the 2005 Ohio Building Code
(OBC). The review was based upon the following criteria:
Use Group: No Change
Occupancy: No Change
Area: No Change
Const. Type: Existing [No Change]
Notes: Proposed alteration and addition of Fire Alarm System devices for the new layout of the
Tenant space.
The fire protective signaling system drawings have been Certified by Robert G. Sines 111, Ohio certification no.
F-032, the fire protection Contractor is Penn Electric Company, Ohio certification #53-25-1191, the installer has
been identified as Robert Eckstein, Certification #54-25-1815, all to comply with the requirements of OBC
Section 105.3 and have been reviewed, therefore, in accord with OBC section 105.3.1.4.
Due to violations of the Ohio Building Code (OBC), which may constitute a serious hazard, the City of Dublin,
Division of Building Standards is unable to issue plan approval at this time without the additional information or
corrections indicated below. This CORRECTION REQUEST LETTER is not a disapproval of the plans, but is
a request for clarification and/or modification of the following items:
The following item(s) shall be brought into full conformance with the OBC prior to the issuance of any
conditional or final plan approval.
1. OBC 907.9 Alarm notification appliances: Alarm notification appliances shall be provided and shall be
listed for their purpose. Audible and visual alarms shall be installed in accordance with the "ADAAG"
and NFPA 72.
ADAAG 4.28.1. Alarm systems required to be accessible shall comply with Section 4.28 ADAAG. At a
minimum, visual signal appliances shall be provided in restrooms and any other general usage areas (e.g.,
meeting rooms, auditoriums, corridors, lobbies and any other area for common use.
City of Dublin FIRE PROTECTION PLAN REVIEW 07-200565(1)
Perimeter West Medical Center - Fire Alarm System November 9, 2007
07-200565(1) Page 2
Provide visual notification appliances in the following "common use" areas:
1. All Exam Room areas including Consult/Exam rooms,
2. All Treatment Rooms,
3. Traction Rooms,
4. Spa and Treatment areas, and
5. Insomnia Clinic areas.
By definition, these areas constitute common use and shall be protected in accordance with the
referenced code sections. Please explain why these rooms would not be provided with visual signal
appliances? Furthermore, audible alarms shall be tested in the field for compliance with Section 90 7.9.2
OBC pursuant to their vicinity to these areas of common use.
This review does not preclude the necessity to conform with provisions which may have been omitted or
overlooked in the review process, but which are requirements of the code. Ultimate responsibility for legal
compliance with the Standards of Safety rest with the registered design professional, the tenant and the owner.
Plan Approval will be valid only upon receipt by the City of Dublin, Division of Building Standards, of one
signed copy of this addendum.
TO REQUEST AN APPEAL HEARING, YOU MUST send a written request, listing the items to be
appealed and the relief sought and on copy of this order to:
Jeffrey S. Tyler, Chief Building Official
City of Dublin, Ohio
5800 Shier Rings Road
Dublin, Ohio 43017-1236
Reviewed and signed,
/M t~vd a
Michael A. Boryca, Architect/Plan Examiner effrey . yler, Chief Building Official
(614) 488-4009 City of D lin, Ohio
Signature - Architect, Engineer, Contractor Date
or Owner
Print Name and Title as Signed
c: Washington Township Fire Department
MAB:Iwb
City of Dublin FIRE PROTECTION PLAN REVIEW 07-200565(1)
architecture! memorandum invoice #07-200565 - 2
OHIO INCORPORATED 454 East Main Street Suite 236 Columbus, Ohio 43215-5380 614.488.4009 fax.488.4005
November 9, 2007 City of Dublin Contract No. PS 01-21-13
Employer Identification No. 31-1413248
City of Dublin
Division of Building Standards
5800 Shier-Rings Road
Dublin, Ohio 43016
Attention: Mr. Jeffrey S. Tyler, Chief Building Official
Plan Review Services for: Perimeter West Medical Center - Fire Alarm System Alterations
6810 Perimeter Drive
CORRECTION REQUEST LETTER #1
Permit No. 07-200565(1)
Labor Cost: Total Number of Hours to be Charged @ $60.00/Hour: 2.5
• Review Time: 1.0
• Administrative Time: 1.5
TOTAL BILLING THIS INVOICE $150.00
This memorandum invoice is being sent as reference for you to prepare the necessary fees for the applicant to
pay. The time spent on this review will be submitted for payment at the end of the month with our usual
invoicing.
Should you have any questions or comments concerning this review, please don't hesitate to contact me.
Thank you for the opportunity to be of service.
Cordially,
architecture
Michael A. Boryca, Architect
Plans Examiner #P001794
~opl!Cant CITY OF DUBLIN; sic n
Division of Building Standards - 5800 Shier-Rings Road • Dublin1=0h1o_430_16__._.__
RECEIVED Phone: (614) 410-4670 • Inspection Line: (61400 r_-
WTFD: (614) 889-2347 V
APR A 2 2007 DG `C 31 NOV 01 2007
BUILDING DIVISION FIRE PROTECTION PERMIT APPLICATION C:t t~ s,,tlUl'eri
CITY OF DUBLI
Application Date Yol 67 Bldg. App. # Fire Protection App.
PR E T I F R ATI N P~k~,He-f~a GI~eI"
Project Address $ ID e i Mefe i ve Project Name Medic-+I CeDt
Owner/Tenant Contact Name Sedno&k ao Telephone Il4 - 45J-17 70
APPLICANT INFORMATION
Fire Protection Contractor eoupJ F aL RiL o
Address N n) R,4 - Ws, 0 6 a l Telephone q -415- 96 9,V
State Certificate Number 3- as ' Ia 1 Dublin Registration Number 616-4
Installer Name Rabeat ck5-'eP.J State Certificate Number
SCOPE OF WORK
(Mark One) New Replace Repaft Alteration
FIRE DETECTI N AND ALARM SYSTEM (Number of Each)
Detectors Strobes la Horns Fire Alarm Boxes Other
SUPPRESSION SYSTEM (Number of Each)
Standpipes On Site Water Piping Sprinkler Heads Limited Area Other
f
FEES s r 1400, 00
'RE DETECTION OR SUPPRESSION PERMIT PR ESSIN4' Ems' •$3ff6b
LOW VOLTAGE PERMIT (DETECTION ONLY) $3Q.60 Minimu'OWNO 00
plus $20.00 each 1,000 sq ft or fraction thereof ov'r 1,000 sq ft b40~ 00
OUTSIDE PLAN REVIEW SERVICES (EXAM11 S FEE AS C 3 0• 00
STATE SURCHARGE (3%) :3 3~600 _-4 r O
TOTAL FEE DUE
This permit is granted on the express conglition that said work shall in all respects, conform to the ordinances of
the City of Dublin and all laws of the Stato of Ohio regulating construction, installation, repair and alteration,
and may be revoked at any time upon violation of any provisions of said laws. This permit conveys no right to
open any street, alley or sidewalk or a ypart thereof, nor to make any connection to a water main.
Signature of Licensed Contractor MXiy A- DATE 41olld7
FOR OFFICIAL USE ONLY
Review Comments: e ' c a ? / '
sc
Ta
s Ae6!!!5j ~S- ZZ kjf&Z doj49W .17 x 4W-f
r 01
e Department: Date: S ~t D
Plans Examiner: ( J - Q Date: b
Issued by CBO: Date:
CITY OF DUBLIN
Division of Building Standards - 5800 Shier-Rings Road - Dublin, Ohio 43016
Phone: (614) 410-4670 - Inspection Line: (614) 410-4680
Application Number . . . . . 07-00200565 Date 5/03/07
Property Address . . . . . . 6810 PERIMETER DR
Parcel Number: 273-011310
Alternate Address: PERIMETER WEST PROF PARK
Tenant nbr, name PERIMETER W MED CTR DECTE
Application type description FIRE PROTECTION
Property owner . . . . . . . PERIMETER WEST PROPERTIES LLC
Contractor . . . . . . . . . BEDROCK GROUP DEVELOPMENT
Permit . . . . . . LOW VOLTAGE ELECTRIC PERMIT
Additional desc . .
Permit Fee . . . . 670.00 Plan Check Fee .00
Issue Date . . . 5, ~f~~ Valuation 0
Expiration Date . 100/07
Qty Unit Charge Per Extension
BASE FEE 30.00
32.00 20.0000 THOU COM ELECTRIC LOW VOLTAGE 640.00
Permit . . . . . . FIRE DETECTION PERMIT
Additional desc . .
Permit Fee . . . . 60.00 Plan Check Fee .00
Issue Date . . . . Valuation . . . . 0
Qty Unit Charge Per Extension
BASE FEE 60.00
Special Notes and Comments
CONTACT WASHINGTON TOWNSHIP FIRE
PREVENTION FOR INSPECTIONS AT 766-0857
Other Fees . . . . . . . . OUTSIDE PLAN REVIEW 240.00
SURCHARGE FEE - ELECTRIC 20.10
SURCHARGE FEE - BLDG 7.20
SURCHARGE FEE - FIRE 1.80
Fee summary Charged Paid Credited Due
Permit Fee Total 730.00 .00 .00 730.00
Plan Check Total .00 .00 .00 .00
Other Fee Total 269.10 .00 .00 269.10
Grand Total 999.10 .00 .00 999.10
This permit is granted on the express condition that said work shall in all r ects,
conform to the ordinances of the City of Dublin and all laws of the State of Ohio
regulating construction, installation, repair and alteration and may be revoked at
any time upon violation of any provisions of law.
CITY OF DUBLIN
Building Standards - 5800 Shier-Rings Road - Dublin, Ohio 43016
Phone: (614) 410-4670 - Inspection Line: (614) 410-4680
Application #07-200565 April 27, 2007
• CONDITIONAL PLAN APPROVAL
FIRE ALARM/DETECTION SYSTEM
THIS IS NOT A BUILDING PERMIT. IT IS A RECORD OF OUR REVIEW OF DOCUMENTS
SUBMITTED WITH YOUR APPLICATION FOR A BUILDING PERMIT.
Re: Perimeter West Medical Center Applicant: Penn Electric Co.,
First Floor & Rest Shell (614) 451-1770
6810 Perimeter Drive Fire Protection Permit No: 07-200565
The Fire Alarm Drawings dated 3/13/07, submitted with the Fire Protection Permit Application, for the
captioned project, has been reviewed for compliance with the provisions of the 2005 Ohio Building Code (OBC).
The review was based upon the following criteria:
Use Group: No Change
Occupancy: No Change
Area: No Change
Const. Type: Existing [No Change]
Notes: Proposed alteration and addition of Fire Alarm System devices for the new layout of the
Tenant space.
The fire protective signaling system drawings have been Certified by Robert G. Sines III, Ohio certification no.
F-032, the fire protection Contractor is Penn Electric Company, Ohio certification #53-25-1191, the installer has
been identified as Robert Eckstein, Certification #54-25-1815, all to comply with the requirements of OBC
Section 105.3 and have been reviewed, therefore, in accord with OBC section 105.3.1.4.
This CONDITIONAL PLAN APPROVAL for the fire protective signaling system only, is issued by the City of
Dublin, Division of Building Standards, in accordance with Section 106.3.1.2 OBC.
The following Items shall be corrected or addressed on or before May 30, 2007 as a condition on this Plan
Approval:
1. OBC 907.1.1 Construction documents. Construction documents for fire alarm systems shall be
submitted for review and approval prior to system installation. Construction documents shall include, but
not be limited to, all of the following:
1. A floor plan which indicates the use of all rooms.
2. Locations of alarm-initiating and notification appliances.
3. Alarm control and trouble signaling equipment.
4. Annunciation.
5. Power connection.
6. Battery calculations.
City of Dublin FIRE PROTECTION PLAN REVIEW 07-200565
Perimeter West Medical Center - Fire Alarm System April 27, 2007
07-200565 Page 2
7. Conductor type and sizes.
8. Voltage drop calculations.
9. Manufacturers, model numbers and listing information for equipment, devices and materials.
10. Details of ceiling height and construction.
11. The interface of fire safety control functions
Please submit information on the Use or Descriptions of the Rooms shown on the first floor, for further
review. This information was missing or was incomplete on the submission made, for our review. Please
submit this information so that we may continue our review of this application..
For the information of the Applicant the following item(s) are required for code compliance, but are not
necessarily covered in detail in the construction documents This list is a reminder to the design professional
and contractors of issues which are to be satisfactorily dealt with in the field:
2. The certificate of approval of fire protection plans shall be posted in a conspicuous location outside of the
building or in the front part of the premises on which is, or will be, located the approved building or
equipment. The owner and the contractor shall, so far as possible, preserve and keep said certificate until
the completion of the work to which the approved construction documents relate; Section 105.7.2 OBC.
3. The proposed construction shall conform to the requirements of Chapter 11 OBC and the "Americans with
Disabilities Act Accessibility Guidelines" (ADAAG).
4. Fire Alarm System cable and wiring located in noncombustible plenums shall meet with the requirements
of Section 907 OBC and Article 760, NFPA 70.
5. Provide a record of completion for each completed fire alarm system in accordance with Section 907.17
and NFPA 72 Completion Documents.
6. Upon completion of the fire protective signaling system, all alarm-initiating devices and circuits, alarm-
indicating appliances and circuits, supervisory-signal initiating devices and circuits, signaling line circuits,
and primary and secondary power supplies shall be subjected to a 100 percent acceptance test in
accordance with NFPA 72A and 72E listed in Chapter 35; Section 907.16 OBC.
7. OBC 907 Acceptance testing: When the installation of the detectors is complete, each detector and all
interconnecting wiring for multiple-station detectors shall be subject to a 100-percent acceptance test in
accordance with the household fire warning equipment provisions of NFPA 72 listed in Chapter 35.
8. No electrical work (conduits, cables or other electrical apparatus) may be covered or concealed without
visual inspection and approval by the electrical field inspector as per OBC 109.
9. The existing electrical conductors, if removed, abandoned, or altered, shall be accomplished to the
electrical field inspectors approval pursuant to the requirements of Section 109 OBC. Electrical work
found not to meet the code's standards shall be corrected to the electrical field inspector's approval.
10. All electrical work will comply with the requirements of Article 27 OBC and the National Electric Code
NFPA 70, OBC approved edition and is subject to the approval of the electrical inspector, in accordance
with Section 109 of the OBC.
City of Dublin FIRE PROTECTION PLAN REVIEW 07-200565
Perimeter West Medical Center - Fire Alarm System April 27, 2007
07-200565
Page 3
TO REQUEST AN APPEAL HEARING, YOU MUST send a written request, listing the items to be
appealed and the relief sought and on copy of this order to:
Jeffrey S. Tyler, Chief Building Official
City of Dublin, Ohio
5800 Shier Rings Road
Dublin, Ohio 43017-1236
THIS RECORD OF OUR REVIEW OF DOCUMENTS IS TO BE SIGNED BY THE OWNER OR
HIS/HER AUTHORIZED AGENT AND RETURNED, ALONG WITH ANY REQUESTED
INFORMATION, TO THIS BUILDING DEPARTMENT BEFORE BEGINNING WORK, BUT NOT
MORE THAN 30 DAYS AFTER ISSUANCE. FAILURE TO COMPLY MAY RESULT IN REVOCATION
OF THE BUILDING PERMIT.
THE SIGNING OF THIS DOCUMENT IS AN AGREEMENT THAT YOU WILL COMPLY WITH ALL
ITEMS LISTED HEREIN. THE COMMENCEMENT OF WORK CONSTITUTES ACCEPTANCE OF ALL
ITEMS LISTED HEREIN.
Reviewed and signed,
ImAad a "
Michael A. Boryca, Architect/Plans Examiner a S. ( ler, Chief Building Official
(614) 488-4009 City o lin, Ohio
Rdx-fi A-"At. S- q-07
Signature - Architect, Engineer ontractor Date
or Owner
R0602+ A- f'e'kS+e"N NES?deout
Print Name and Title as Signed
c: Washington Township Fire Department
MAB:Iwb
City of Dublin FIRE PROTECTION PLAN REVIEW 07-200565
CITY OF DUBLIN
Division of Building Standards - 5800 Shier-Rings Road - Dublin, Ohio 43016
Phone: (614) 410-4670 - Inspection Line: (614) 410-4680
Application Number . . . . . 07-00200565 Date 5/03/07
Property Address . . . . . . 6810 PERIMETER DR
Parcel Number: 273-011310
Alternate Address: PERIMETER WEST PROF PARK
Tenant nbr, name PERIMETER W MED CTR DECTE
Application type description FIRE PROTECTION
Property owner . . . . . . . PERIMETER WEST PROPERTIES LLC
Contractor . . . . . . . . . BEDROCK GROUP DEVELOPMENT
Permit . . . . LOW VOLTAGE ELECTRIC PERMIT
Additional desc . .
Permit Fee 670.00 Plan Check Fee .00
Issue Date . . . .6V Valuation 0
Expiration Date lafl/07
Qty Unit Charge Per Extension
BASE FEE 30.00
32.00 20.0000 THOU COM ELECTRIC LOW VOLTAGE 640.00
Permit . . . . FIRE DETECTION PERMIT
Additional desc . .
Permit Fee . . . . 60.00 Plan Check Fee .00
Issue Date . . . . Valuation . . . . 0
Qty Unit Charge Per Extension
BASE FEE 60.00
Special Notes and Comments
CONTACT WASHINGTON TOWNSHIP FIRE
PREVENTION FOR INSPECTIONS AT 766-0857
Other Fees . . . . . OUTSIDE PLAN REVIEW 240.00
SURCHARGE FEE - ELECTRIC 20.10
SURCHARGE FEE - BLDG 7.20
SURCHARGE FEE - FIRE 1.80
Fee summary Charged Paid Credited Due
Permit Fee Total 730.00 .00 .00 730.00
Plan Check Total .00 .00 .00 .00
Other Fee Total 269.10 .00 .00 269.10
Grand Total 999.10 .00 .00 999.10
This permit is granted on the express condition that said work shall in all r ects,
conform to the ordinances of the City of Dublin and all laws of the State of Ohio
regulating construction, installation, repair and alteration and may be revoked at
any time upon violation of any provisions of law.
CITY OF DUBLIN
Building Standards - 5800 Shier-Rings Road - Dublin, Ohio 43016
Phone: (614) 410-4670 - Inspection Line: (614) 410-4680
Application #07-200565 April 27, 2007
CONDITIONAL PLAN APPROVAL
FIRE ALARM/DETECTION SYSTEM
THIS IS NOT A BUILDING PERMIT. IT IS A RECORD OF OUR REVIEW OF DOCUMENTS
SUBMITTED WITH YOUR APPLICATION FOR A BUILDING PERMIT.
Re: Perimeter West Medical Center Applicant: Penn Electric Co.,
First Floor & Rest Shell (614) 451-1770
6810 Perimeter Drive Fire Protection Permit No: 07-200565
The Fire Alarm Drawings dated 3/13/07, submitted with the Fire Protection Permit Application, for the
captioned project, has been reviewed for compliance with the provisions of the 2005 Ohio Building Code (OBC).
The review was based upon the following criteria:
Use Group: No Change
Occupancy: No Change
Area: No Change
Const. Type: Existing [No Change]
Notes: Proposed alteration and addition of Fire Alarm System devices for the new layout of the
Tenant space.
The fire protective signaling system drawings have been Certified by Robert G. Sines III, Ohio certification no.
F-032, the fire protection Contractor is Penn Electric Company, Ohio certification #53-25-1191, the installer has
been identified as Robert Eckstein, Certification #54-25-1815, all to comply with the requirements of OBC
Section 105.3 and have been reviewed, therefore, in accord with OBC section 105.3.1.4.
This CONDITIONAL PLAN APPROVAL for the fire protective signaling system only, is issued by the City of
Dublin, Division of Building Standards, in accordance with Section 106.3.1.2 OBC.
The following items shall be corrected or addressed on or before May 30, 2007 as a condition on this Plan
Approval.
1. OBC 907.1.1 Construction documents. Construction documents for fire alarm systems shall be
submitted for review and approval prior to system installation. Construction documents shall include, but
not be limited to, all of the following:
1. A floor plan which indicates the use of all rooms.
2. Locations of alarm-initiating and notification appliances. b
3. Alarm control and trouble signaling equipment.
4. Annunciation.
5. Power connection.
6. Battery calculations.
City of Dublin FIRE PROTECTION PLAN REVIEW 07-200565
Perimeter West Medical Center - Fire Alarm System April 27, 2007
07-200565
Page 2
7. Conductor type and sizes.
8. Voltage drop calculations.
9. Manufacturers, model numbers and listing information for equipment, devices and materials.
10. Details of ceiling height and construction.
11. The interface of fire safety control functions
Please submit information on the Use or Descriptions of the Rooms shown on the first floor, for further
review. This information was missing or was incomplete on the submission made, for our review. Please
submit this information so that we may continue our review of this application.
For the information of the Applicant the following item(s) are required for code compliance, but are not
necessarily covered in detail in the construction documents. This list is a reminder to the design professional
and contractors of issues which are to be satisfactorily dealt with in the field:
2. The certificate of approval of fire protection plans shall be posted in a conspicuous location outside of the
building or in the front part of the premises on which is, or will be, located the approved building or
equipment. The owner and the contractor shall, so far as possible, preserve and keep said certificate until
the completion of the work to which the approved construction documents relate; Section 105.7.2 OBC.
3. The proposed construction shall conform to the requirements of Chapter 11 OBC and the "Americans with
Disabilities Act Accessibility Guidelines" (ADAAG).
4. Fire Alarm System cable and wiring located in noncombustible plenums shall meet with the requirements
of Section 907 OBC and Article 760, NFPA 70.
5. Provide a record of completion for each completed fire alarm system in accordance with Section 907.17
and NFPA 72 Completion Documents.
6. Upon completion of the fire protective signaling system, all alarm-initiating devices and circuits, alarm-
indicating appliances and circuits, supervisory-signal initiating devices and circuits, signaling line circuits,
and primary and secondary power supplies shall be subjected to a 100 percent acceptance test in
accordance with NFPA 72A and 72E listed in Chapter 35; Section 907.16 OBC.
7. OBC 907 Acceptance testing: When the installation of the detectors is complete, each detector and all
interconnecting wiring for multiple-station detectors shall be subject to a 100-percent acceptance test in
accordance with the household fire warning equipment provisions of NFPA 72 listed in Chapter 35.
8. No electrical work (conduits, cables or other electrical apparatus) may be covered or concealed without
visual inspection and approval by the electrical field inspector as per OBC 109.
9. The existing electrical conductors, if removed, abandoned, or altered, shall be accomplished to the
electrical field inspectors approval pursuant to the requirements of Section 109 OBC. Electrical work
found not to meet the code's standards shall be corrected to the electrical field inspector's approval.
10. All electrical work will comply with the requirements of Article 27 OBC and the National Electric Code
NFPA 70, OBC approved edition and is subject to the approval of the electrical inspector, in accordance
with Section 109 of the OBC.
City of Dublin FIRE PROTECTION PLAN REVIEW 07-200565
Perimeter West Medical Center - Fire Alarm System
07-200565 April 27, 2007
Page 3
Page 3
TO REQUEST AN APPEAL HEARING, YOU MUST send a written request, listing the items to be
appealed and the relief sought and on copy of this order to:
Jeffrey S. Tyler, Chief Building Official
City of Dublin, Ohio
5800 Shier Rings Road
Dublin, Ohio 43017-1236
THIS RECORD OF OUR REVIEW OF DOCUMENTS IS TO BE SIGNED BY THE OWNER OR +
HIS/HER AUTHORIZED AGENT AND RETURNED,
INFORMATION, TO THIS BUILDING DEPARTMENT BEFOALONG WITH ANY
RE BEGINNING O EQESTOT
MORE THAN 30 DAYS AFTER ISSUANCE. FAILURE TO COMPLY MAY RESULT IN REVOCATION
OF THE BUILDING PERMIT.
THE SIGNING OF THIS DOCUMENT IS AN AGREEMENT THAT YOU WILL COMPLY WITH ALL
ITEMS LISTED HEREIN, THE COMMENCEMENT OF WORK CONSTITUTES ACCEPTANCE OF ALL
ITEMS LISTED HEREIN.
Reviewed and signed,
llwAzda' 131h,
Michael A. Boryca, Architect/Plans Examiner
(614) 488-4009 a S. ler, Chief Building Official
Crty o lin, Ohio
Signature - Architect, En ' S - y - 0
gmeer ontr ctor Date
or Owner
Robes+ A- 6'4kS}c;0j PRFS.-deNt
Print Name and Title as Signed
c: Washington Township Fire Department
MAB:Iwb
City of Dublin FIRE PROTECTION PLAN REVIEW
07-200565