HomeMy WebLinkAboutOrdinance 077-17Davton Legal Blank_ Inc.
Ordinance No.
RECORD OF ORDINANCES
77-17
Form No. 30043
Passed , 20
AN ORDINANCE, PURSUANT TO SECTION 731.231 OF THE OHIO
REVISED CODE, ADOPTING A STANDARD CODE KNOWN AS
THE "INTERNATIONAL FIRE CODE/2015" PERTAINING TO
FIRE, FIRE HAZARDS, AND FIRE PREVENTION AS PREPARED
AND PROMULGATED BY THE INTERNATIONAL CODE
COUNCIL (ICC) A PUBLIC OR PRIVATE ORGANIZATION
PUBLISHING A MODEL OR STANDARD CODE, AND REPEALING
THE ORDINANCE OF THE EXISTING FIRE CODE.
WHEREAS, the City of Dublin is authorized by Section 731.231 of the Ohio Revised Code to
adopt by incorporation by reference a standard code pertaining to fire, fire hazards, and fire
prevention prepared and promulgated by a public or private organization that publishes a model
or standard code; and
WHEREAS, the International Fire Code/2015 as published by the International Code Council
(ICC) has been reviewed and recommended for adoption with some change and amendment by
the Fire Chief and Fire Safety Inspector of the Washington Township Fire Department; and
WHEREAS, it is the consensus of the City Council that adoption of such code by reference and
as recommended is necessary and desirable.
NO HEREFORE, BE IT ORDAINED by the Council of the City of Dublin, State of Ohio,
of the elected members concurring, that:
Section 1. Adoption of International Fire Code/2015
That, pursuant to ORC Section 731.231, a certain document, three (3) copies of which are on file
in the office of the Clerk of Council of the City of Dublin, Ohio being marked and designated as
the "International Fire Code/2015," including Appendix Chapters B, C, and D as published by
the International Code Council (ICC), is hereby adopted by incorporation by reference as the Fire
Code of the City of Dublin, Ohio and each and all of the regulations, provisions, penalties,
conditions, and terms of the "International Fire Code/2015," subject to any modification herein,
are hereby referred to, adopted and made apart hereof, .as if fully set out in this Ordinance.
Section 2. Fire Chief Designated Code Official
For the purpose of enforcing this code, where the term Code Official is used throughout the
adopted code it shall mean the Chief of the Washington Township Fire Department or his duly
appointed Fire Inspector within the Division of Fire Prevention in such Fire Department. The
Chief of the Fire Department or the Commander of the Division of Fire Prevention or the duly
appointed Fire Safety Inspector shall have full authority to perform any of the duties or acts which
are required or authorized to be performed by the Code Official.
Section 3. Additions, Insertions and Changes
That the International Fire Code/2015 and the appendices thereto adopted by this ordinance are
amended and changed in the following respects [The Ohio Administrative Code (OAC)]:
Section 101.1: City of Dublin, Ohio
Section 105.6 -
Section 105.6 Required operational permits. Section 105.6.16 shall be deleted
in its entirety. The following permit fee table is set for the operational permits
spelled out in Section 105.6. The operational permits spelled out in Section 105.6
shall be issued annually by the Washington Township Fire Department and the
Washington Township Fire Department shall collect fees.
Washington Township Fire Department
Operational Permit Type Section No. Amount
Aerosol Products
105.6.1
$50.00
Arnusement Buildings
105.6.2
$100.00
Aviation Facilities
105.6.3
$100.00
Carliivals and Fairs
105.6.4
$100.00
Dayton Legal Blank, Inc.
77-17
Ordinance No.
RECORD OF ORDINANCES
Form No. 30043
Page 2of5
Passed , 20
Battery Systems
105.7.2
$40.00
Cellulose Nitrate Film
10 5.6.5
$100.00
Combustible Dust -Producing Operations
105.6.6
$100.00
Combustible Fibers
105.6.7
$100.00
Compressed. Gases
105.6.8
$40.00
Covered Mall Buildings
105.6.9
$200.00
Cryogenic Fluids
105.6.10
$100.00
Cutting and welding
l 0 5.6.1 1
$40.00
Ory Cleaning Plants
10.5.6.12
$40.00
Exhibits and Trade Shows
105.6.13
:$100.00
Explosives
105.6.14
$100.00
Fireworks Exhibition (OFC) FM -31.07.1
105.6.14
$500.00
Fire Hvdrants and valves
105.6.15
NIA
Flammable and Combustible Liquids
105.6.16
Paragraph A -To in -stall-, remove, repair or alter a stationary
tank forthe storage of flammable or combustible liquids or
modify or replace any line ordispensing device connected
$100.00
thereto.
Paragraphs B, C, D, E and G
$40.00
(B) For the storage, handling or use of Class 1. liquids
exceeding 5 gallons (19L) in an. institutional or residential.
occupancy, or exceeding 10 gallons (38L) in any other
occupancy, or exceeding 60 gallons (227L) outside of any
building, except that a permit shall not be required for the
following purposed:
(i) For the storage or use of flammable liquids in the fuel
tank of a motor vehicle, aircraft, motorboat, mobile power
plant or mobile heating plant.
(ii) For the storage or use of paints, oils, varnishes or
similar mixtures when such liquids are stored for painting,
maintenance, or similar purposes on the premises and are
not stored for a period exceeding 30 days.
(iii) For the storage or use of flammable liquids for
operational purposes in equipment and. machinery.
(C) For the storage or use of Class II combustible liquids or
Class III combustible liquids exceeding 25 gallons (95L) in a
structure, except for fuel oil utilized in connection with oil -
burning equipment in single-family residential occupancies or
for the storage or use of Class II or Class III combustible
liquids for operational. purposes in equipment or machinery.
(D) For the manufacture, processing, blending or
refining of flammable or combustible liquids.
(E) For the storage of flammable or combustible liquids in
stationary tanks.
(G) For any structure utilized for servicing or repairing; a
motor vehicle therein.
Paragraph F -For placing in any flammable or combustible
liquid stationary tank temporarily or permanent out -of -service
and to place a tank back into service [see paragraphs G(2)
(FM -2807.2.1) and (H) ( 11) (FM -2808.1 1) of this rule.
$20.00
Floor Finishing
105.6.17 $40.00
Fruit Crop Ripening
105.6.18 $40.00
Fumigation and Thermal. Insecticide fogging
105.6.19 $40.00
Hazardous Materials
105.6.20 $100.00
HPM Facilities
105.6.21 $100.00
High -Piled Storage
105.6.22 $100.00
Hot work Operations
10 5.6.23) $40.00
Industrial Ovens
105.6.24 $40.00
Lumber yards and woodworking Plants
105.6.25 $100.00
Liquid -or -Gas Fueled Vehicles or equipment in Assembly
105.6.26 $100.00
Buildings
L -P Gas
105.6.27 $100.00
Magnesium
1.05.6.28 $100.00
Miscellaneous Combustible Storage
105.6.29 $100.00
Open Burning
105.6.30 $50.00
Open Flames and Candles
105.6.32 $20.00
Organic Coatings
1.05.6.33 .$100.00
Place of Assembly
105.6.34 $50.00
Private Fire Hydrants
10 5.6.3 5 $2 () . () ()
Dayton Legal Blank, Inc.
77-17
Ordinance No.
RECORD OF ORDINANCES
Form No. 30043
Page 3 of 5
Passed .20
Pyrotechnic Special Effects Material (OFC) FM -31 19.1
1.05.6.36
,$250.00
Pyroxylin Plastics
10.5.6.37
$1.00.00
Refrigeration 1 Jct uipment
105.6.338
$100.00
Fire Alarm and Detection Systems and Related
105.7.5
.See Section
Repair Garages and Service Stations
105.6.39
105.6. 17
Rooftop 1-leliports
105.6.40
$300.00
Spraying or Dipping
105.6.41
$40.00
Storage of Scrap Tires and "Wire Byproducts
105.6.42
$100.00
"Femporary Membrane Structures, Tents and Canopies
105.6.43
$1.00.00
1 to 5 Tents
105.7.7
$50.00
6 to 10 Tents
10S.7.10
$75.00
11 to 15 Tents
105.7.1 1
$100.00
16 to 20 Tents
105.7. 1.2
$150.00
20 or More Tents
105.7.13
$200.00
Tire -Rebuilding Plants
105.6.44
$100.00
Waste Handling
105.6.45
$200.00
Wood Products
105.6.46
$40.00
Cortin" UK '7•
Section 105.7 Required construction permits. The code official is authorized
to issue construction permits for work as set forth in Sections 105.7. I
through 105.7.12, inclusive. Requirements for construction permits shall 1 be
coordinated with the Code Official.
Washington Township Fire Department
Permit Type
Section No.
Amount
Automatic Fire -extinguishing Systems
105.7. l
$100.00
Compressed Gases
1.05.7.;
$ 40.00
Fire Alarm and Detection Systems and Related
105.7.5
$ .50.00
Equipment
Fire Pumps and Related Equipment:
105.7.6
$ 50.00
Flammable and Combustible Liquids
105.7.7
See Secrron
105.6.17
Hazardous Materials
105.7.8
$1.00.00
Industrial. Ovens
105.7.7
$ 40.00
LP -Gas
10S.7.10
$100.00
Private Fire f lydrants
105.7.1 1
$ 20.00
Spraying or Dipping
105.7. 1.2
$ 40.00
Standpipe Systems
105.7.13
$ 50.00
Temporary Membrane Structures, Tents and
105.7. 14
See Section
Canopies
105.6.43
Cpl -fin" 100 A -
Section 109.3 Violation penalties. Persons who shall violate a provision of this
code or who shall fail to comply with any of the requirements thereof or who
shall erect, install, alter, repair or do work in violation of the approved
construction documents or directive of the code official or of a permit or
certificate used under provisions of this code shall be guilty of a minor
misdemeanor pursuant to R.C. Section 505.374 and R.C. Section 505.99,
punishable by a fine of not more than one hundred dollars. Each day that a
violation continues after due notice has been served shall be deemed a separate
offense.
C�t•tinr� 111 d•
Section 111.4 Failure to comply. Any person who shall continue any work after
having been served with a stop work order, except such work as that person is
directed to perform to remove a violation or tinsafe condition, shall be guilty
of a rninol• ni.isdenleanor pursuant to R.C. Section 505.374 and R.C. Section
505.99, and liable to a fine of not more than one hundred dollars. Each day that
such work confit -ales after due noti.ce has been served shall be deemed a separate
offense.
Dayton Legal Blank, Inc.
77-17
Ordinance No.
RECORD OF ORDINANCES
Section D103IFC
Form No. 30043
Page 4 of 5
Passed , 20
Section 0103.3 Turning radius. The turning radius on any fire apparatus access
road public or private that provides access to a structure or equipment, shall be a
minimum turning radius of 45 feet on the outside and 25 feet on the inside.
Public or private dead end roads or driveways shall have a cul-de-sac with a
minimum radius of 40 feet to the back of the curb. Any common access drive, or
public or private dead end road or driveway exceeding 300 feet in length, shall
have a tum around with a minimum outside radius of 50 feet to the back of the
curb.
Section 505.391
Section 505.391 False Alarms.
(A) If, after the fire department of a township, township fire district, or joint fire
district, or a private fire company with which the fire department of a township,
township fire district, or joint fire district contracts for fire protection, responds
to a false alarm from an automatic fire alarm system at a commercial
establishment or residential building, the board of township trustees gives written
notice by certified mail that it may assess a charge of up to three hundred dollars
for each subsequent false alarm occurring after three false alarms by that system
within the same calendar year, the board of township trustees may assess that
charge. This notice shall be mailed to the owner and the lessee, if any, of the
building in which the system is installed. After the board gives this notice, the
board need not give any additional written notices before assessing a charge for
a false alarm as provided by this section.
(13) If payment of the bill assessing a charge for a false alarm is not received
within thirty days, the township fiscal officer shall send a notice by certified mail
to the manager and to the owner, if different, of the real estate of which the
commercial establishment is a part, or to the occupant, lessee, agent, or tenant
and to the owner, if different, of the real estate of which the residential building
is a part, indicating that failure to pay the bill within thirty days, or to show just
cause why the bill should not be paid within thirty days, will result in the
assessment of a lien upon the real estate in the amount of the bill. If payment is
not received or j ust cause for nonpayment is not shown within those thirty days,
the amount of the bill shall be entered upon the tax duplicate, shall be a lien upon
the real estate from the date of the entry, and shall be collected as other taxes and
returned to the township treasury to be earmarked for use for fire services.
(C) As used in this section, "commercial establishment" means a building or
buildings in an area used primarily for nonresidential, commercial purposes.
Effective Date: 09-17-1986; 08-17-2006.
Section 506.1
Section 506.1 When required. When a property is protected by an automatic
alarm system, and access to or within a structure, or an area on that property is
unduly difficult because of secured openings, and where immediate access is
necessary for life saving or firefighting purposes, the code official is authorized
to require a key box to be installed in an accessible location. The key box shall
be an approved type. The key box shall contain:
a) Keys to locked points of ingress, whether on the interior or
exterior of such building.
b) Keys to locked mechanical equipment rooms.
C) Keys to locked electrical rooms.
d) Keys to elevator controls.
e) Keys to other areas or directed by the code official.
This section shall not apply to any residential units.
Dayton Legal Blank, Inc.
77-17
Ordinance No.
RECORD OF ORDINANCES
Passed
Page 5 of 5
Form No. 30043
20
Section 507.3 Fire flow. Fire flow requirements for buildings or portions of
buildings and facilities shall comply with "International Fire Code 2015
Appendix B."
Chapter 9: Fire Protection Systems: amend by insertion of new Section 914, titled
General, which shall consist of the contents of OAC 1301:7-7-05 (A) Section FM -500-0,
which is hereby adopted by reference for enforcement by the code official.
Chapter 9: Fire Protection Systems: amend, by insertion of new Section 915, titled
Definitions, which shall consist of the contents of OAC 1301:7-7-05(B) Section FM -
5 01.0, which is hereby adopted by reference for enforcement by the code official.
Chapter 33: Explosives and Fireworks; delete chapter and adopt OAC 1301: 7-7-31 by
reference for enforcement by the . code official as stipulated therein.
Chapter 34: Flammable and combustible liquid: delete chapter and adopt OAC 1301:7-
7-28 by reference for enforcement by the code official as stipulated therein.
All references within the International Fire Code/2015 or the appendices thereto adopted
by this ordinance, to the International Building Code, or a section thereof, shall be
changed and interpreted to refer to the provision(s) of the current Ohio Building Code
governing the same topic or matter, whether or not such provision(s) are in agreement
with the provisions of the International Building Code.
All references within the International Fire Code/2015 or the appendices thereto
adopted by this ordinance, to the International Mechanical Code, or a section thereof,
shall be changed and interpreted to refer to the provisions(s) of the current O-
Mechanical Code governing the same topic or matter, whether or not such provision(s)
are in agreement with the provisions of the International Mechanical Code,
All references within the International Fire Code/2015 or the appendices hereto
adopted by this ordinance, to the International Plumbing Code, or a section thereof,
shall be changed and interpreted to refer to the provision(s) of the current Ohio Plumbing
Code governing the same topic or matter, whether or not such provision(s) are in
agreement with the provisions of the International Plumbing Code.
Section 4. Inconsistent Resolutions Repealed
That Ordinance 31-03, adopting the existing fire code, passed on April 7, 2003 and all other
ordinances or parts of ordinances in conflict herewith are hereby repealed.
Section 5. Effective Date.
ThisAdinance shall be of ive upon the earliest date permitted by law.
PWsd this ..� D� �y /f���C� ����d�, 2017
Mayor - PresidMg
ATTEST:
Clerk of Council
Office of the City Manager
6200 Emerald Parkway s Dublin, OH 43017
Ci of Dublin Phone: 614,410.4400 + Fax: 614.410,4490
Memo
To, Members of Dublin City Council
From; Dana L ,McDaniel, City Manager �e
Date: November 3, 2017
Initiated By; Donna Goss, Director of Development
Re: Ordinance 77-17 - Adoption of International Fire Code/2015
Background
Pursuant to Section 505,373 of the Ohio Revised Code, on August 8, 2017, the Washington
Township Board of Trustees adopted a Standard Code known as the International Fire Code/2015
pertaining to fire, Fre hazards, and fire prevention. The City of Dublin is authorized by Section
737.37 of the Ohio Revised Code to adopt by incorporation by reference such code.
Changes and amendments from the existing Code are outlined in Section 3 of the ordinance. The
minor modifications are generally administrative in nature with the exception of Section 505.391.
False Alarms. As written, the township trustees have the ability to "assess a charge of up to three
hundred dollars for each subsequent false alarm occurring after three false alarms by that system
within the same calendar year," Prior written notice will be given regarding the authority to assess
the charge and mailed to the owner and the lessee of the building in which the system is installed,
Payments of charges not received within thirty days will result in a lien upon the property in the
amount of the bill,
Recommendation
Staff recommends approval of Ordinance 77-17 at the second reading/public hearing on November
20, 2017,
►107/:4:3
FIRE -FLOW REQUIREMENTS FOR BUILDINGS
The provisions contained in this appendix are not mandatory unless specifically referenced in the adopting ordinance.
SECTION B101
GENERAL
B101.1 Scope. The procedure for determining fire -flow
requirements for buildings or portions of buildings hereafter
constructed shall be in accordance with this appendix. This
appendix does not apply to structures other than buildings.
SECTION B102
DEFINITIONS
B102.1 Definitions. For the purpose of this appendix, certain
terms are defined as follows:
FIRE -FLOW. The flow rate of a water supply, measured at
20 pounds per square inch (psi) (138 kPa) residual pressure,
that is available for fire fighting.
FIRE -FLOW CALCULATION AREA. The floor area, in
square feet (mz), used to determine the required fire flow.
SECTION B103
MODIFICATIONS
B103.1 Decreases. The fire chief is authorized to reduce the
fire -flow requirements for isolated buildings or a group of
buildings in rural areas or small communities where the
development of full fire -flow requirements is impractical.
B103.2 Increases. The fire chief is authorized to increase the
fire -flow requirements where conditions indicate an unusual
susceptibility to group fires or conflagrations. An increase
shall not be more than twice that required for the building
under consideration.
B103.3 Areas without water supply systems. For informa-
tion regarding water supplies for fire -fighting purposes in
rural and suburban areas in which adequate and reliable water
supply systems do not exist, the fire code official is autho-
rized to utilize NFPA 1142 or the International Wildland-
Urban Interface Code.
SECTION B104
FIRE -FLOW CALCULATION AREA
B104.1 General. The fire -flow calculation area shall be the
total floor area of all floor levels within the exterior walls,
and under the horizontal projections of the roof of a building,
except as modified in Section B 104.3.
B104.2 Area separation. Portions of buildings which are
separated by fire walls without openings, constructed in
accordance with the International Building Code, are allowed
to be considered as separate fire -flow calculation areas.
B104.3 Type IA and Type IB construction. The fire -flow
calculation area of buildings constructed of Type IA and
Type IB construction shall be the area of the three largest suc-
cessive floors.
Exception: Fire -flow calculation area for open parking
garages shall be determined by the area of the largest
floor.
SECTION B105
FIRE -FLOW REQUIREMENTS FOR BUILDINGS
B105.1 One- and two-family dwellings, Group R-3 and R-
4 buildings and townhouses. The minimum fire -flow and
flow duration requirements for one- and two-family dwell-
ings, Group R-3 and R-4 buildings and townhouses shall be
as specified in Tables B 105.1(1) and B 105.1(2).
B105.2 Buildings other than one- and two-family dwell-
ings, Group R-3 and R-4 buildings and townhouses. The
minimum fire -flow and flow duration for buildings other than
one- and two-family dwellings, Group R-3 and R-4 buildings
and townhouses shall be as specified in Tables 13105.2 and
B 105.1(2).
TABLE B105.1(1)
REQUIRED FIRE -FLOW FOR ONE- AND TWO-FAMILY DWELLINGS, GROUP R-3 AND R-4 BUILDINGS AND TOWNHOUSES
FIRE -FLOW CALCULATION AREA
AUTOMATIC SPRINKLER SYSTEM
MINIMUM FIRE -FLOW
FLOW DURATION
(square feet)
(Design Standard)
(gallons per minute)
(hours)
0-31600
No automatic sprinkler system
1,000
1
3,601 and greater
No automatic sprinkler system
Value in Table
Duration in Table B105.1(2)
B105.1(2)
at the required fire -flow rate
0-31600
Section 903.3.1.3 of the International Fire Code or
500
'/z
Section P2904 of the International Residential Code
3,601 and greater
Section 903.3.1.3 of the International Fire Code or
/ value in Table
z
1
Section P2904 of the International Residential Code
B105.1(2)
For Sl: 1 square foot = 0.0929 mZ, 1 gallon per minute = 3.785 L/m,
L1»41!191E41
TABLE B105.1(2)
REFERENCE TABLE FOR TABLES B105.1(1) AND B105.2
Type IA and IB'
FIRE -FLOW CALCULATION AREA (square feet)
Type IIA and IIIA' Type IV and V-A' Type IIB and IIIB'
Type V -B'
FIRE -FLOW
(gallons per minute)'
FLOW DURATION
(hours)
0-22,700
0-12,700
0-8,200
0-5,900
0-3,600
1,500
22,701-30,200 12,701-17,000 8,201-10,900 5,901-7,900 3,601-4,800 1,750
30,201-38,700
17,001-21,800
10,901-12,900
7,901-9,800
4,801-6,200
2,000
2
38,701-48,300 21,801-24,200 12,901-17,400 9,801-12,600 6,201-7,700 2,250
48,301-59,000 24,201-33,200 17,401-21,300 12,601-15,400 7,701-9,400 2,500
59,001-70,900
33,201-39,700
21,301-25,500
15,401-18,400
9,401-11,300
2,750
70,901-83,700
39,701-47,100
25,501-30,100
18,401-21,800
11,301-13,400
3,000
3
83,701-97,700 47,101-54,900 30,101-35,200 21,801-25,900 13,401-15,600 3,250
97,701-112,700 54,901-63,400 35,201-40,600 25,901-29,300 15,601-18,000 3,500
112,701-128,700
63,401-72,400
40,601-46,400
29,301-33,500
18,001-20,600
3,750
128,701-145,900
72,401-82,100
46,401-52,500
33,501-37,900
20,601-23,300
4,000
145,901-164,200
82,101-92,400
52,501-59,100
37,901-42,700
23,301-26,300
4,250
164,201-183,400 92,401-103,100 59,101-66,000 42,701-47,700 26,301-29,300 4,500
183,401-203,700 103,101-114,600 66,001-73,300 47,701-53,000 29,301-32,600 4,750
203,701-225,200
114,601-126,700
73,301-81,100
53,001-58,600
32,601-36,000
5,000
225,201-247,700
126,701-139,400
81,101-89,200
58,601-65,400
36,001-39,600
5,250
247,701-271,200
139,401-152,600
89,201-97,700
65,401-70,600
39,601-43,400
5,500
4
271,201-295,900 152,601-166,500 97,701-106,500 70,601-77,000 43,401-47,400 5,750
295,901 -Greater 166,501 -Greater 106,501-115,800 77,001-83,700 47,401-51,500 6,000
-
-
115,801-125,500
83,701-90,600
51,501-55,700
6,250
125,501-135,500 90,601-97,900 55,701-60,200 6,500
-
-
135,501-145,800
97,901-106,800
60,201-64,800
6,750
-- 145,801-156,700 106,801-113,200 64,801-69,600 7,000
-
-
156,701-167,900
113,201-121,300
69,601-74,600
7,250
-
-
167,901-179,400
121,301-129,600
74,601-79,800
7,500
179,401-191,400
129,601-1.38,300
79,801-85,100
7,750
- - 191,401 -Greater 138,301 -Greater 85,101 -Greater 8,000
For SI: 1 square foot = 0 0929 mZ, 1 gallon per minute = 3.785 L/m, 1 pound per square inch = 6.895 kPa_
a. Types of construction are based on the International Building Code.
b. Measured at 20 psi residual pressure_
TABLE B105.2
REQUIRED FIRE -FLOW FOR BUILDINGS OTHER THAN ONE- AND
TWO-FAMILY DWELLINGS, GROUP R-3 AND R-4 BUILDINGS AND TOWNHOUSES
AUTOMATIC SPRINKLER SYSTEM
(Design Standard)
MINIMUM FIRE -FLOW FLOW DURATION
(gallons per minute) (hours)
No automatic sprinkler system
Value in Table B105.1(2) Duration in Table B105.1(2)
Section 903.3.1.1 of the International Fire Code
25% of the value in Table B 105.1(2)' Duration in Table B 105.1(2) at the reduced flow rate
Section 903.3.1.2 of the International Fire Code
25% of the value in Table BI05.1(2)b Duration in Table B105.1(2) at the reduced flow rate
For SI: 1 gallon per minute = 3 785 L/m
a_ The reduced fire -flow shall be not less than 1,000 gallons per minute
b. The reduced fire -flow shall be not less than 1,500 gallons per minute
APPENDIX B
13105.3 Water supply for buildings equipped with an auto-
matic sprinkler system. For buildings equipped with an
approved automatic sprinkler system, the water supply shall
be capable of providing the greater of:
1. The automatic sprinkler system demand, including hose
stream allowance.
2. The required fire -flow
SECTION B106
REFERENCED STANDARDS
ICC
IBC -15 International Building Code
B104.2,
Tables
ICC
IFC -15 International Fire Code
B105.1(1) and
B105.2
ICC
IWUIC-15 International Wildland-
B103.3
Urban Interface Code
ICC
IRC -15 International Residential
Table
Code
B105.1(1)
Standard on Water Supplies
NFPA
1142-12 for Suburban and Rural Fire
B103.3
Fighting
APPENDIX C
FIRE HYDRANT LOCATIONS AND DISTRIBUTION
The provisions contained in this appendix are not mandatory unless specifically referenced in the adopting ordinance.
SECTION C101
GENERAL
C101.1 Scope. In addition to the requirements of Section
507.5.1 of the International Fire Code, fire hydrants shall be
provided in accordance with this appendix for the protection
of buildings, or portions of buildings, hereafter constructed or
moved into the jurisdiction.
SECTION C102
NUMBER OF FIRE HYDRANTS
C102.1 Minimum number of fire hydrants for a building.
The number of fire hydrants available to a building shall be
not less than the minimum specified in Table C102.1.
SECTION C103
FIRE HYDRANT SPACING
C103.1 Hydrant spacing. Fire apparatus access roads and
public streets providing required access to buildings in accor-
dance with Section 503 of the International Fire Code shall
be provided with one or more fire hydrants, as determined by
Section C102.1. Where more than one fire hydrant is
required, the distance between required fire hydrants shall be
in accordance with Sections C 103.2 and C 103.3.
C103.2 Average spacing. The average spacing between fire
hydrants shall be in accordance with Table C 102.1.
Exception: The average spacing shall be permitted to be
increased by 10 percent where existing fire hydrants pro-
vide all or a portion of the required number of fire
hydrants.
C103.3 Maximum spacing. The maximum spacing between
fire hydrants shall be in accordance with Table C 102.1.
SECTION C104
CONSIDERATION OF EXISTING FIRE HYDRANTS
C104.1 Existing fire hydrants. Existing fire hydrants on
public streets are allowed to be considered as available to
meet the requirements of Sections C102 and C103. Existing
fire hydrants on adjacent properties are allowed to be consid-
ered as available to meet the requirements of Sections C102
and C103 provided that a fire apparatus access road extends
between properties and that an easement is established to pre-
vent obstruction of such roads.
TABLE C102.1
REQUIRED NUMBER AND SPACING OF FIRE HYDRANTS
FIRE -FLOW REQUIREMENT
(gpm)
MINIMUM NUMBER
OF HYDRANTS
AVERAGE SPACING
BETWEEN HYDRANTS..b..,''9
(feet)
MAXIMUM DISTANCE FROM ANY
POINT ON STREET OR ROAD
FRONTAGE TO A HYDRANT" 9
1,750 or less
1
500
250
2,000-2,250
2
450
225
2,500
3
450
225
3,000
3
400
225
3,500-4,000
4
350
210
4,500-5,000
5
300
180
5,500
6
300
180
6,000
6
250
150
6,500-7,000
7
250
1150
7,500 or more
8 or more'
200
1120
For SI: 1 foot = 304.8 mm, 1 gal [on per minute = 3 785 L/m.
a. Reduce by 100 feet for dead-end streets or roads.
b, Where streets are provided with median dividers that cannot be crossed by fire fighters pulling hose lines, or where arterial streets are provided with four or
more traffic lanes and have a traffic count of more than 30,000 vehicles per day, hydrant spacing shall average 500 feet on each side of the street and be
arranged on an alternating basis.
c. Where new water mains are extended along streets where hydrants are not needed for protection of structures or similar fire problems, fire hydrants shall be
provided at spacing not to exceed 1,000 feet to provide for transportation hazards_
d. Reduce by 50 feet for dead-end streets or roads,
e. One hydrant for each 1,000 gallons per minute or fraction thereof.
f A 50 -percent spacing increase shall be permitted where the building is equipped throughout with an approved automatic sprinkler system in accordance with
Section 903.3,1-1 of the International Fire Code_
g. A 25 -percent spacing increase shall be permitted where the building is equipped throughout with an approved automatic sprinkler system in accordance with
Section 903.3.1.2 or 903.3-13 of the International Fire Code or Section P2904 of the International Residential Code.
APPENDIX C
SECTION C105
REFERENCED STANDARDS
ICC IFC -15 International Fire Code C101.1
C103.1
Table
C102.1
ICC IRC -15 International Residential Code Table
C102.1
APPENDIX D
FIRE APPARATUS ACCESS ROADS
The provisions contained in this appendix are not mandatory unless specifically referenced in the adopting ordinance.
SECTION D101
GENERAL
D101.1 Scope. Fire apparatus access roads shall be in accor-
dance with this appendix and all other applicable require-
ments of the International Fire Code.
SECTION D102
REQUIRED ACCESS
D102.1 Access and loading. Facilities, buildings or portions
of buildings hereafter constructed shall be accessible to fire
department apparatus by way of an approved fire apparatus
access road with an asphalt, concrete or other approved driv-
ing surface capable of supporting the imposed load of fire
apparatus weighing at least 75,000 pounds (34 050 kg).
SECTION D103
MINIMUM SPECIFICATIONS
D103.1 Access road width with a hydrant. Where a fire
hydrant is located on a fire apparatus access road, the mini-
mum road width shall be 26 feet (7925 mm), exclusive of
shoulders (see Figure D103.1).
For SI: 1 toot= 304.8 mm
100' -- --
28' min.
100 -Foot Diameter
Cul-de-sac
D103.2 Grade. Fire apparatus access roads shall not exceed
10 percent in grade.
Exception: Grades steeper than 10 percent as approved by
the fire chief.
D103.3 Turning radius. The minimum turning radius shall
be determined by the fire code official.
D103.4 Dead ends. Dead-end fire apparatus access roads in
excess of 150 feet (45 720 mm) shall be provided with width
and turnaround provisions in accordance with Table D103.4.
TABLE D103.4
REQUIREMENTS FOR DEAD-END
FIRE APPARATUS ACCESS ROADS
LENGTH
(feet)
WIDTH
(feet)
TURNAROUNDS REQUIRED
0-150
28
None required
120 -foot Hammerhead, 60 -foot "Y" or
151-500
28
96 -foot diameter cul-de-sac in accor-
dance with Figure D103.1
120 -foot Hammerhead, 60 -foot "Y" or
501-750
28
96 -foot diameter cul-de-sac in accor-
dance with Figure D103.1
Over 750
Special approval required
For SI: 1 foot = 304.8 mm.
80'—
75" R
(typ) 28' min.
70'
20'
A
25'R
(tyyp•)
28' min.
70 -foot Hammerhead
80 -foot Diameter
Cul-de-sac
FIGURE D103.1
DEAD-END FIRE APPARATUS ACCESS ROAD TURNAROUND
APPENDIX D
D103.5 Fire apparatus access road gates. Gates securing
the fire apparatus access roads shall comply with all of the
following criteria:
1. Where a single gate is provided, the gate width shall be
not less than 20 feet (6096 mm). Where a fire apparatus
road consists of a divided roadway, the gate width shall
be not less than 12 feet (3658 mm).
2. Gates shall be of the swinging or sliding type.
3. Construction of gates shall be of materials that allow
manual operation by one person.
4. Gate components shall be maintained in an operative
condition at all times and replaced or repaired when
defective.
5. Electric gates shall be equipped with a means of open-
ing the gate by fire department personnel for emer-
gency access. Emergency opening devices shall be
approved by the fire code official.
6. Methods of locking shall be submitted for approval by
the fire code official.
7. Electric gate operators, where provided, shall be listed
in accordance with UL 325.
8. Gates intended for automatic operation shall be
designed, constructed and installed to comply with the
requirements of ASTM F 2200.
D103.6 Signs. Where required by the fire code official, fire
apparatus access roads shall be marked with permanent NO
PARKING—FIRE LANE signs complying with Figure
D103.6. Signs shall have a minimum dimension of 12 inches
(305 mm) wide by 18 inches (457 mm) high and have red let-
ters on a white reflective background. Signs shall be posted
on one or both sides of the fire apparatus road as required by
Section D 103.6.1 or D 103.6.2.
SIGN TYPE "A" SIGN TYPE "C" SIGN TYPE "D"
NO NO NO
PARKING PARKING PARKING
FIRE LANE FIRE LANE FIRE LANE 18
12 12" 12° ., —
FIGURE D103.6
FIRE LANE SIGNS
D103.6.1 Roads 20 to 26 feet in width. Fire lane signs as
specified in Section D103.6 shall be posted on both sides
of fire apparatus access roads that are 20 to 26 feet wide
(6096 to 7925 mm).
D103.6.2 Roads more than 26 feet in width. Fire lane
signs as specified in Section D103.6 shall be posted on one
side of fire apparatus access roads more than 26 feet wide
(7925 mm) and less than 32 feet wide (9754 mm).
SECTION D104
COMMERCIAL AND INDUSTRIAL DEVELOPMENTS
D104.1 Buildings exceeding three stories or 30 feet in
height. Buildings or facilities exceeding 30 feet (9144 mm)
or three stories in height shall have at least two means of fire
apparatus access for each structure.
D104.2 Buildings exceeding 62,000 square feet in area.
Buildings or facilities having a gross building area of more
than 62,000 square feet (5760 mz) shall be provided with two
separate and approved fire apparatus access roads.
Exception: Projects having a gross building area of up to
124,000 square feet (11 520 mZ) that have a single
approved fire apparatus access road when all buildings are
equipped throughout with approved automatic sprinkler
systems.
D104.3 Remoteness. Where two fire apparatus access roads
are required, they shall be placed a distance apart equal to not
less than one half of the length of the maximum overall diag-
onal dimension of the lot or area to be served, measured in a
straight line between accesses.
SECTION D105
AERIAL FIRE APPARATUS ACCESS ROADS
D105.1 Where required. Where the vertical distance
between the grade plane and the highest roof surface exceeds
30 feet (9144 mm), approved aerial fire apparatus access
roads shall be provided. For purposes of this section, the
highest roof surface shall be determined by measurement to
the eave of a pitched roof, the intersection of the roof to the
exterior wall, or the top of parapet walls, whichever is
greater.
D105.2 Width. Aerial fire apparatus access roads shall have
a minimum unobstructed width of 26 feet (7925 mm), exclu-
sive of shoulders, in the immediate vicinity of the building or
portion thereof.
D105.3 Proximity to building. At least one of the required
access routes meeting this condition shall be located within a
minimum of 15 feet (4572 mm) and a maximum of 30 feet
(9144 mm) from the building, and shall be positioned parallel
to one entire side of the building. The side of the building on
which the aerial fire apparatus access road is positioned shall
be approved by the fire code official.
D105.4 Obstructions. Overhead utility and power lines shall
not be located over the aerial fire apparatus access road or
between the aerial fire apparatus road and the building. Other
obstructions shall be permitted to be placed with the approval
of the fire code official.
APPENDIX D
SECTION D106
SECTION D108
MULTIPLE -FAMILY RESIDENTIAL DEVELOPMENTS
REFERENCED STANDARDS
D106.1 Projects having more than 100 dwelling units.
ASTM F 2200-13 Standard Specification for
Multiple -family residential projects having more than 100
Automated Vehicular Gate
dwelling units shall be equipped throughout with two sepa-
Construction D103.5
rate and approved fire apparatus access roads.
1CC IFC -15 International Fire Code D101.1,
Exception: Projects having up to 200 dwelling units may
D107.1
have a single approved fire apparatus access road when all
UL 325-02 Door, Drapery, Gate, Louver,
buildings, including nonresidential occupancies, are
and Window Operators and
equipped throughout with approved automatic sprinkler
Systems, with Revisions
systems installed in accordance with Section 903.3.1.1 or
through June 2013 D103.5
903.3.1.2.
D106.2 Projects having more than 200 dwelling units.
Multiple -family residential projects having more than 200
dwelling units shall be provided with two separate and
approved fire apparatus access roads regardless of whether
they are equipped with an approved automatic sprinkler sys-
tem.
D106.3 Remoteness. Where two fire apparatus access roads
are required, they shall be placed a distance apart equal to not
less than one-half of the length of the maximum overall diag-
onal dimension of the property or area to be served, measured
in a straight line between accesses.
SECTION D107
ONE- OR TWO-FAMILY
RESIDENTIAL DEVELOPMENTS
D107.1 One- or two-family dwelling residential develop-
ments. Developments of one- or two-family dwellings where
the number of dwelling units exceeds 30 shall be provided
with two separate and approved fire apparatus access roads.
Exceptions:
1. Where there are more than 30 dwelling units on a
single public or private fire apparatus access road
and all dwelling units are equipped throughout with
an approved automatic sprinkler system in accor-
dance with Section 903.3.1.1, 903.3.1.2 or 903.3.1.3
of the International Fire Code, access from two
directions shall not be required.
2. The number of dwelling units on a single fire appa-
ratus access road shall not be increased unless fire
apparatus access roads will connect with future
development, as determined by the fire code official.
D107.2 Remoteness. Where two fire apparatus access roads
are required, they shall be placed a distance apart equal to not
less than one-half of the length of the maximum overall diag-
onal dimension of the property or area to be served, measured
in a straight line between accesses.